Application range of the HEM approach for CO2 expansion inside two-phase ejectors for supermarket refrigeration systems

被引:80
作者
Palacz, Michal [1 ]
Smolka, Jacek [1 ]
Fic, Adam [1 ]
Bulinski, Zbigniew [1 ]
Nowak, Andrzej J. [1 ]
Banasiak, Krzysztof [2 ]
Hafner, Armin [2 ]
机构
[1] Silesian Tech Univ, Inst Thermal Technol, PL-44100 Gliwice, Poland
[2] SINTEF Energy, N-7465 Trondheim, Norway
关键词
HEM; R744; Ejector; Two-phase; CO2; Ejector efficiency; COMPUTATIONAL MODEL; R744; EJECTOR; PERFORMANCE;
D O I
10.1016/j.ijrefrig.2015.07.006
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, the accuracy of the homogeneous equilibrium (HEM) applied to 3-D CFD-based simulations of CO2 expansion inside two-phase ejectors is presented. The HEM approach previously reported in the literature was assessed by comparing the computed and measured mass flow rates that pass through an ejector motive nozzle. In addition, the HEM approach implemented using CFD was tested over a vast range of ejector operating regimes. To ensure that all of the computations were performed consistently, a validated CFD model combined within an in-house developed script was used. The comparison of the experimental and computational results showed that the HEM accuracy varied for the different sets of operating parameters. Accurate results were obtained for operating regimes near or above the CO2 critical point. The model accuracy decreased with the decreasing temperature and decreasing distance to the saturation line. (C) 2015 Elsevier Ltd and International Institute of Refrigeration. All rights reserved.
引用
收藏
页码:251 / 258
页数:8
相关论文
共 22 条