Component-based, gray-box modeling of ductless multi-split heat pump systems

被引:12
作者
Cheung, Howard [1 ]
Braun, James E. [1 ]
机构
[1] Purdue Univ, Sch Mech Engn, Ray W Herrick Labs, W Lafayette, IN 47907 USA
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2014年 / 38卷
关键词
Multi-split heat pump; Ductless heat pump; Variable-speed heat pump; Modeling; Performance analysis; PERFORMANCE;
D O I
10.1016/j.ijrefrig.2013.10.007
中图分类号
O414.1 [热力学];
学科分类号
摘要
Multi-split ductless heat pumps are touted as an energy efficient option for air conditioning and heating in residential and small commercial applications. However, their use of multiple indoor units with variable speed compressor and fans and complicated controls leads to difficulties in understanding their characteristics by experiments only. A method to model the system using gray-box component models and an empirical control algorithm is described in this paper. The model was constructed from experimental results of an 8 kW R410A dual-unit ductless heat pump system having an accumulator. Strategies for modeling systems with accumulators and saturated control inputs are presented. Parametric studies with varying indoor air temperature, individual indoor unit load ratio, indoor fan speed and total indoor load were conducted. The results show that the model predicts system performance accurately and can help to understand the effect of saturated control inputs and changes of accumulator status on system performance. (C) 2013 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:30 / 45
页数:16
相关论文
共 19 条
[1]  
[Anonymous], 2007, Introduction to Heat Transfer
[2]   Variable refrigerant flow systems: A review [J].
Aynur, Tolga N. .
ENERGY AND BUILDINGS, 2010, 42 (07) :1106-1112
[3]  
Bell I., 2010, ACHP VERSION 1 3 SOF
[4]  
Braun J.E., 1989, ASHRAE Transactions, V95, P164
[5]   Capacity modulation of an inverter-driven multi-air conditioner using electronic expansion valves [J].
Choi, JM ;
Kim, YC .
ENERGY, 2003, 28 (02) :141-155
[6]  
CHURCHILL SW, 1977, CHEM ENG-NEW YORK, V84, P91
[7]  
EPRI, 2013, MIN UN HEAT PERF EV
[8]  
Jahnig D.I., 2000, ASHRAE T, V106, P122
[9]   Performance characteristics of a simultaneous cooling and heating multi-heat pump at partial load conditions [J].
Joo, Youngju ;
Kang, Hoon ;
Ahn, Jae Hwan ;
Lee, Mooyeon ;
Kim, Yongchan .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (04) :893-901
[10]   Experimental study on the performance of a simultaneous heating and cooling multi-heat pump with the variation of operation mode [J].
Kang, Hoon ;
Joo, Younju ;
Chung, Hyunjoon ;
Kim, Yonychan ;
Choi, Jongmin .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (06) :1452-1459