Fractional transmission line model of oil-immersed transformer windings considering the frequency-dependent parameters

被引:8
|
作者
Liang, Guishu [1 ]
Gao, Shiqiang [1 ]
Wang, Yanchao [2 ]
Zang, Ying [3 ]
Liu, Xin [1 ]
机构
[1] North China Elect Power Univ, Dept Elect Engn, Baoding, Peoples R China
[2] Datong Shanxi Power Supply Co, State Grid Elect Power Co, Datong, Peoples R China
[3] Shandong Elect Engn & Equipment Grp CO LTD, Jinan, Peoples R China
基金
中国国家自然科学基金;
关键词
transformer windings; transformer oil; finite element analysis; skin effect; permittivity; impedance parameter; admittance parameter; complex permittivity variation; fractional transmission line model; oil-paper samples; Cole-Cole model; single dielectric relaxation process; structure coefficient per unit length; finite element software; FEMM; fractional admittance PUL; frequency-dependent parameters; oil-immersed transformer windings; FAST TRANSIENTS; INSULATION; SIMULATION;
D O I
10.1049/iet-gtd.2016.0877
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The frequency-dependent characteristics of the impedance parameter and the admittance parameter in the transmission line model of the transformer windings (TWs) are mainly result of the skin effect of the conductor and the complex permittivity's variation with the frequency of oil-paper, respectively. In this study, an accurate fractional transmission line model of TWs considering the frequency-dependent parameters is proposed. The measured permittivity of oil-paper samples is fitted based on the Cole-Cole model with single dielectric relaxation process, and then simplify the fitting model. The structure coefficient per unit length (PUL) corresponding to the complex capacitance of the TWs can be obtained based on the finite element software FEMM. Combining the simplified model with the structure coefficient, the fractional admittance PUL of TWs is derived. Then the fractional transmission line model of the TWs is determined. Finally, the calculated results of fractional transmission line model considering the frequency-dependent parameters are compared with the experimental measurements, and the results demonstrate the accuracy of the proposed model.
引用
收藏
页码:1154 / 1161
页数:8
相关论文
共 50 条
  • [31] Improvement and Application of Dynamic Thermal Circuit Model for Oil-Immersed Power Transformer
    Zhu, Lingyu
    Li, Hualong
    Yao, Xiu
    Ji, Shengchang
    2014 IEEE INTERNATIONAL POWER MODULATOR AND HIGH VOLTAGE CONFERENCE (IPMHVC), 2014, : 591 - 594
  • [32] A Generalized Approach for Multifrequency Transmission Line Transformer With Frequency-Dependent Complex Source and Load
    Liu, Liang
    Jin, Ronghong
    Liang, Xianling
    Fan, Haijun
    Bai, Xudong
    Zhou, Han
    Geng, Junping
    Zhu, Weiren
    IEEE TRANSACTIONS ON MICROWAVE THEORY AND TECHNIQUES, 2019, 67 (09) : 3603 - 3616
  • [33] Fault Diagnosis Model of Oil-immersed Transformer Based on Return Voltage Measurement
    Chen, Ming
    Hu, Shuilian
    Mo, Zhenhua
    2008 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION, VOLS 1 AND 2, 2009, : 72 - 76
  • [34] Fault Diagnosis Model of Oil-immersed Transformer Based on Return Voltage Measurement
    Chen Ming
    Hu Shui-lian
    Mo Zhen-hua
    2008 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION, VOLS 1 AND 2, 2009, : 313 - 317
  • [35] Application of frequency domain spectroscopy to the insulation diagnosis of oil-immersed power transformer on site
    Zhang, Zhi
    Dong, Ming
    Yang, Shuang-Suo
    Jiang, Wei
    Zhang, Guan-Jun
    Yan, Zhang
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (07): : 1648 - 1653
  • [36] Fast calculation of temperature distribution in oil-immersed transformer windings based on U-net neural network
    Liu, Yunpeng
    Gao, Yiqian
    Liu, Gang
    Hu, Wanjun
    Wang, Wenhao
    Wang, Bowen
    AIP ADVANCES, 2023, 13 (03)
  • [37] Fast Calculation of Flow-thermal Coupling Model of Oil-immersed Transformer Windings Based on U-net Neural Network
    Liu Y.
    Gao Y.
    Liu G.
    Hu W.
    Wang W.
    Wang B.
    Gao C.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2024, 44 (07): : 2897 - 2909
  • [38] Frequency dependent and Nonuniform Parameters Transmission Line Model
    Wardzinska, Agnieszka
    Bandurski, Wojciech
    2016 IEEE 20TH WORKSHOP ON SIGNAL AND POWER INTEGRITY (SPI), 2016,
  • [39] On the Computation of Frequency-Dependent Core and Proximity Effects for Transient Analysis of Transformer Windings
    Alkraimeen, Yazid
    Gomez, Pablo
    IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (03) : 891 - 898
  • [40] Validation of frequency-dependent transmission line models
    Gustavsen, B
    IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) : 925 - 933