Experimental investigation on R134a vapour ejector refrigeration system

被引:136
作者
Selvaraju, A. [1 ]
Mani, A. [1 ]
机构
[1] Indian Inst Technol, Dept Mech Engn, Refrigerat & Airconditioning Lab, Madras 600036, Tamil Nadu, India
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2006年 / 29卷 / 07期
关键词
refrigeration system; ejector system; R134a; experiment; performance;
D O I
10.1016/j.ijrefrig.2006.01.004
中图分类号
O414.1 [热力学];
学科分类号
摘要
The experimental investigation of the performance of a vapour ejector refrigeration system is described. The system uses R134a as working fluid and has a rated cooling capacity of 0.5 kW. The influence of generator, evaporator and condenser temperatures on the system performance is studied. This kind of system can be operated with low grade thermal energy such as solar energy, waste heat, etc. The operating conditions are chosen accordingly as, generator temperature between 338 K and 363 K, condenser temperature between 299 K and 310.5 K, and evaporator temperature between 275 K and 285.5 K. Six configurations of ejectors of different geometrical dimensions are selected for the parametric study. The performance of the refrigeration system at different operating temperatures is presented. (c) 2006 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:1160 / 1166
页数:7
相关论文
共 14 条
[11]   Comparative study of the performance of an ejector refrigeration cycle operating with various refrigerants [J].
Sun, DW .
ENERGY CONVERSION AND MANAGEMENT, 1999, 40 (08) :873-884
[12]  
Sun DW, 1996, INT J ENERG RES, V20, P871, DOI 10.1002/(SICI)1099-114X(199610)20:10<871::AID-ER201>3.0.CO
[13]  
2-4
[14]  
ZEREN F, 1978, ASME WINT ANN M, P1