Validation of EMT Digital Twin Models for Dynamic Voltage Performance Assessment of 66 kV Offshore Transmission Network

被引:14
作者
Ganesh, Saran [1 ]
Perilla, Arcadio [1 ]
Torres, Jose Rueda [1 ]
Palensky, Peter [1 ]
van der Meijden, Mart [1 ,2 ]
机构
[1] Delft Univ Technol, Dept Elect Sustainable Energy, Mekelweg 4, NL-2628 CD Delft, Netherlands
[2] TenneT TSO BV, NL-6812 AR Arnhem, Netherlands
来源
APPLIED SCIENCES-BASEL | 2021年 / 11卷 / 01期
关键词
Direct Voltage Control; EMT; Offshore Wind Farm; digital twin model;
D O I
10.3390/app11010244
中图分类号
O6 [化学];
学科分类号
0703 ;
摘要
The increase in Power Electronic (PE) converters due to the increase in offshore wind energy deployment have given rise to technical challenges (e.g., due to unprecedented fast dynamic phenomena) related to voltage and frequency stability in the power system. In the Offshore Wind Farms (OWFs), the currently available current injection-based voltage control for PE converters are not suitable for voltage control in PE dominated systems due to the absence of continuous voltage control and ineffectiveness during islanding. Moreover, in such power systems, the conventional controllers are not suitable for frequency control due to the absence of dynamic frequency control. The paper presents the Direct Voltage Control (DVC) strategy in a real-time environment to mitigate challenges related to voltage and frequency stability during islanding of OWFs. The control strategy is implemented in the average Electro-magnetic Transient (EMT) model of Type-4 Wind Generator (WG) in RSCAD(R) Version 5.011.1. It is compared with the benchmark model of the control strategy in DIgSILENT PowerFactory(TM) 2019 SP2 (x64) in EMT platform. The comparison based on short-term voltage stability and reactive current injection reveals that both the models provide similar results, confirming the validation of the RSCAD model. Moreover, the detailed representation of the converters in the RSCAD model provides a better depiction of the real-world operation.
引用
收藏
页码:1 / 19
页数:19
相关论文
共 23 条
[1]   Power Sharing Control Strategy of Multiterminal VSC-HVDC Transmission Systems Utilizing Adaptive Voltage Droop [J].
Abdelwahed, Mohamed Abdelaziz ;
El-Saadany, Ehab F. .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2017, 8 (02) :605-615
[2]  
[Anonymous], 2017, TECHNICAL REPORT
[3]  
[Anonymous], 2014, Guide for the Development of Models for HVDC Converters in a HVDC Grid
[4]  
Barnes A., 2020, Can the current EU regulatory framework deliver decarbonisation of gas?
[5]   A Review of Passive Power Filters for Three-Phase Grid-Connected Voltage-Source Converters [J].
Beres, Remus Narcis ;
Wang, Xiongfei ;
Liserre, Marco ;
Blaabjerg, Frede ;
Bak, Claus Leth .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2016, 4 (01) :54-69
[6]  
Bouzid AE, 2016, PROCEEDINGS OF 2016 8TH INTERNATIONAL CONFERENCE ON MODELLING, IDENTIFICATION & CONTROL (ICMIC 2016), P701, DOI 10.1109/ICMIC.2016.7804202
[7]  
DNV GL, 2015, 66 KV SYST OFFSH WIN
[8]  
Duckwitz D., 2019, THESIS U KASSEL, DOI [10.17170/kobra-20190510451, DOI 10.17170/KOBRA-20190510451]
[9]  
Duckwitz D., 2017, P EN STROMV SYST SYS
[10]  
Erlich I., 2018, DESCRIPTION MODELLIN