Three-Dimensional FDTD Calculation of Lightning-Induced Voltages on a Multiphase Distribution Line With the Lightning Arresters and an Overhead Shielding Wire

被引:66
作者
Tatematsu, Akiyoshi [1 ]
Noda, Taku [1 ]
机构
[1] Cent Res Inst Elect Power Ind, Yokosuka, Kanagawa 2400196, Japan
关键词
Finite-difference time-domain (FDTD) method; lightning protection; lightning-induced voltages; power distribution lines; NUMERICAL ELECTROMAGNETIC ANALYSIS; CIRCUIT SIMULATION; REPRESENTATION; MODEL; FORMULATION; EQUATIONS; BOUNDARY;
D O I
10.1109/TEMC.2013.2272652
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
To suppress the lightning-induced voltages on a distribution line, lightning arresters and/or overhead shielding wire can be installed, and the effectiveness of these countermeasures are usually studied by simulations. Traditionally, field-to-transmission line coupling techniques based on the distributed-parameter circuit theory are used for the calculation of the lightning-induced voltages. Recently, the finite-difference time-domain (FDTD) method that directly and numerically solves Maxwell's equations was applied to the calculation of the lightning-induced voltages. Compared with the conventional methods, the FDTD-based calculation is advantageous in terms of the modeling of inhomogeneous ground parameters, 3-D structures, and grounding systems. But, in the previous works, the distribution line was simulated simply by a single-phase line. Moreover, the representation of lightning arresters in the FDTD method was not yet established. This paper proposes a technique to incorporate the lightning arresters in the FDTD-based lightning overvoltage calculations. In this technique, the voltage-current relationships of the lightning arresters are represented by piecewise linear curves, which can be obtained directly from the data sheets or measured results. For validation purpose, the lightning-induced voltages on a three-phase distribution line equipped with the lightning arresters and a multipoint-grounded overhead shielding wire are calculated by the proposed method, and the results are compared with those obtained by the conventional method and a very good agreement is found.
引用
收藏
页码:159 / 167
页数:9
相关论文
共 56 条
[1]   TRANSIENT-RESPONSE OF MULTI-CONDUCTOR TRANSMISSION-LINES EXCITED BY A NONUNIFORM ELECTROMAGNETIC-FIELD [J].
AGRAWAL, AK ;
PRICE, HJ ;
GURBAXANI, SH .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 1980, 22 (02) :119-129
[2]  
Alaee R., 2008, P 29 INT C LIGHTN PR
[3]   Voltages induced on an overhead wire by lightning strikes to a nearby tall grounded object [J].
Baba, Y ;
Rakov, VA .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2006, 48 (01) :212-224
[4]   On the transmission line model for lightning return stroke representation [J].
Baba, Y ;
Rakov, VA .
GEOPHYSICAL RESEARCH LETTERS, 2003, 30 (24) :ASC13-1
[5]  
Baricum M. V., 1972, UCRL51277 LAWR LIV L
[6]   Accurate and efficient circuit simulation with lumped-element FDTD technique [J].
Ciampolini, P ;
Mezzanotte, P ;
Roselli, L ;
Sorrentino, R .
IEEE TRANSACTIONS ON MICROWAVE THEORY AND TECHNIQUES, 1996, 44 (12) :2207-2215
[7]  
Harrington R.F, 1968, FIELD COMPUTATION MO
[8]   Analytical formulation of lightning-induced voltages on multiconductor overhead lines above lossy ground [J].
Hoidalen, HK .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2003, 45 (01) :92-100
[9]   LIGHTNING-INDUCED VOLTAGE ON AN OVERHEAD WIRE DEPENDENT ON GROUND CONDUCTIVITY [J].
ISHII, M ;
MICHISHITA, K ;
HONGO, Y ;
OGUMA, S .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (01) :109-115
[10]   NUMERICAL SOLUTION OF 2-DIMENSIONAL SCATTERING PROBLEMS USING A TRANSMISSION-LINE MATRIX [J].
JOHNS, PB ;
BEURLE, RL .
PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1971, 118 (09) :1203-+