Locating Partial Discharge Source Occurring on Transformer Bushing by Using the Improved TDOA Method

被引:0
作者
Tian, Ye [1 ]
Qi, Bo [2 ]
Zhuo, Ran [1 ]
Fu, Mingli [1 ]
Li, Chengrong [2 ]
机构
[1] China Southern Power Grid, Elect Power Res Inst, Guangzhou, Guangdong, Peoples R China
[2] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing, Peoples R China
来源
2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD) | 2016年
关键词
partial discharge (PD); localization; transformer bushing; improved time difference of arrival (TDOA) method;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Partial discharge (PD) caused by degradation of insulting materials of electric power equipment is a symptom of breakdown. Furthermore, the electromagnetic (EM) wave emitted from PD interfere the surrounding environment. For avoiding the insulating breakdown and obtaining a better EM environment, it is necessary to detect and locate PD position as soon as possible. In general, from the waveforms of EM waves received by an antenna array, the PD source position can be located by applying the time difference of arrival (TDOA)-based methods. However, owing to noises and multipath waves, the estimation accuracy of the TDOA may decrease, and the location accuracy will be degraded. In the previous study, an improved TDOA estimation technique had been proposed and its applicability for source localization on distribution line was confirmed. In order to further test, in this paper, the proposed technique is applied to estimate the TDOAs from the EM waves which emitted from the PD occurring on transformer bushing. It is shown that the estimation TDOA and source localization results are better than the results by applying the traditional estimation methods.
引用
收藏
页码:144 / 147
页数:4
相关论文
共 13 条
[1]  
Boggs S. A., 1990, IEEE Electrical Insulation Magazine, V6, P33, DOI 10.1109/57.63057
[2]   3-D localization of ultra-wideband impulsive noise sources [J].
Hirata, A ;
Morimoto, T ;
Kawasaki, Z .
2003 IEEE INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY (EMC), VOLS 1 AND 2, SYMPOSIUM RECORD, 2003, :896-899
[4]   GENERALIZED CORRELATION METHOD FOR ESTIMATION OF TIME-DELAY [J].
KNAPP, CH ;
CARTER, GC .
IEEE TRANSACTIONS ON ACOUSTICS SPEECH AND SIGNAL PROCESSING, 1976, 24 (04) :320-327
[5]   Radiometric location of partial discharge sources on energized high-voltage plant [J].
Moore, PJ ;
Portugues, IE ;
Glover, IA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (03) :2264-2272
[6]  
Peck CH, 2001, IEEE T ELECTROMAGN C, V43, P149, DOI 10.1109/15.925534
[7]   RF-Based Partial Discharge Early Warning System for Air-Insulated Substations [J].
Portugues, Iliana E. ;
Moore, Philip J. ;
Glover, Ian A. ;
Johnstone, Carl ;
McKosky, Ralph H. ;
Goff, Mark B. ;
van der Zel, Luke .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (01) :20-29
[8]   Partial discharge location based on time difference of energy accumulation curve of multiple signals [J].
Tang, J. ;
Xie, Y. .
IET ELECTRIC POWER APPLICATIONS, 2011, 5 (01) :175-180
[9]   Partial discharge location in power transformers using wideband RF detection [J].
Tang, Zhiguo ;
Li, Chengrong ;
Cheng, Xu ;
Wang, Wei ;
Li, Jinzhong ;
Li, Jun .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (06) :1193-1199
[10]  
Tian Y., 2012, CIGRE SC C4 HAK C, P223