Field demonstration of a first constant-temperature thermal response test with both heat injection and extraction for ground source heat pump systems

被引:22
|
作者
Jia, Jie [1 ]
Lee, W. L. [2 ]
Cheng, Yuanda [1 ]
机构
[1] Taiyuan Univ Technol, Dept Built Environm & Energy Utilizat Engn, Taiyuan, Shanxi, Peoples R China
[2] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Peoples R China
基金
中国国家自然科学基金;
关键词
Borehole heat exchanger; Field demonstration; Ground source heat pump; Ground thermal conductivity; Heat transfer; Thermal response test; LINE-SOURCE MODEL; PARAMETER-ESTIMATION; BAYESIAN-INFERENCE; EXCHANGERS; RESISTANCE; ERROR;
D O I
10.1016/j.apenergy.2019.04.145
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Getting an accurate estimate of site-specific ground thermal conductivity from thermal response tests (TRTs) is crucial to the efficient and sustainable use of ground source heat pump systems. In a conventional TRT, the ground thermal conductivity is estimated by perturbing the ground with a positive heat injection and the response is measured in time. Despite the simplicity, the conventional TRT does not take into account the ground thermal response to cooling pulses. This may lead to mode-biased estimation due to the presence of natural convective effect. To address the problem, a constant-temperature TRT that comprises simultaneous heat injection and extraction was proposed. A test data analysis method was developed based on the finite line-source model. On this basis, a very first field test was performed in Taiyuan, China, demonstrating the use of the proposed TRT concept with full-scale measurements. Results show that, in the case of this field test, the ground thermal conductivities derived separately from heat injection and heat extraction are 1.83 W/(m K) and 1.65 W/(m K), respectively. The significant difference (10.9%) indicates that when heat injection is involved, the natural convective effect has enhanced ground heat transfer to increase the conductivity estimate. Thus, as compared to the conventional approach, the use of the proposed TRT can improve the characterization of the ground thermal response and conductivity. Relevant results and the test protocol reported in this study will be useful in providing the background information for this technology to be adopted in the ground source heat pump industry.
引用
收藏
页码:79 / 86
页数:8
相关论文
共 50 条
  • [21] TEST METHOD RESEARCH OF SOIL THERMAL CONDUCTIVITY OF GROUND SOURCE HEAT PUMP BASED ON THREE-DIMENSIONAL DISTRIBUTED THERMAL RESPONSE TEST HEAT TRANSFER MODEL
    Deng Z.
    Nian Y.
    Cheng W.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2023, 44 (04): : 259 - 265
  • [22] Research and Development of Thermal Properties Test Device of Deep Ground Soil for Ground Source Heat Pump
    Lian, Zhiwei
    Yu, Xin
    Chen, Jianping
    Pan, Li
    6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 1801 - 1807
  • [23] Numerical analysis of ground temperature response characteristics of a space-heating ground source heat pump system by utilizing super-long flexible heat pipes for heat extraction
    Liu, Hao
    Wang, Xiaoyuan
    Wang, Kai
    Zhu, Yalu
    Zhu, Yuezhao
    ENERGY AND BUILDINGS, 2021, 244
  • [24] Evaluation of thermal imbalance of ground source heat pump systems in residential buildings in China
    Qian, Mingyang
    Yan, Da
    An, Jingjing
    Hong, Tianzhen
    Spitler, Jeffrey D.
    BUILDING SIMULATION, 2020, 13 (03) : 585 - 598
  • [25] Thermal response of ground for different depths on vertical ground source heat pump system in Elazig, Turkey
    Esen, H.
    Inalli, M.
    JOURNAL OF THE ENERGY INSTITUTE, 2009, 82 (02) : 95 - 101
  • [26] Iller bank-Atasehir-building ground source heat pump system and thermal response test - case study
    Cetin, Aysegul
    Isik, Orhan
    Cetin, Suheyla
    Kadioglu, Yusuf K.
    Paksoy, Halime
    BULGARIAN CHEMICAL COMMUNICATIONS, 2016, 48 : 27 - 30
  • [27] Evaluation of thermal imbalance of ground source heat pump systems in residential buildings in China
    Mingyang Qian
    Da Yan
    Jingjing An
    Tianzhen Hong
    Jeffrey D. Spitler
    Building Simulation, 2020, 13 : 585 - 598
  • [28] Thermal performance analysis of ground source heat pump system for low-temperature waste heat recovery storage
    Wang, Songqing
    Qu, Rongyan
    Zhang, Xuedan
    Li, Yitong
    Chen, Jingya
    CASE STUDIES IN THERMAL ENGINEERING, 2022, 35
  • [29] The characteristics of soil temperature field variation of ground source heat pump in severe cold area
    Li, Bai
    Yang, Li
    PROCEEDINGS OF THE 2015 INTERNATIONAL FORUM ON ENERGY, ENVIRONMENT SCIENCE AND MATERIALS, 2015, 40 : 624 - 628
  • [30] Operation performance test and energy efficiency analysis of ground-source heat pump systems
    Gao, Bo
    Zhu, Xiaoyue
    Yang, Xiaojiao
    Yuan, Yanping
    Yu, Nanyang
    Ni, Ji
    JOURNAL OF BUILDING ENGINEERING, 2021, 41