Modifying the control design of DFIG-based wind turbines in order to inhibit power system oscillations

被引:4
作者
Jafarian, Mohammad [1 ]
Asefi, Mohammad-Naser [1 ]
机构
[1] Niroo Res Inst, Power Syst Studies Grp, Tehran, Iran
来源
JOURNAL OF ENGINEERING-JOE | 2019年 / 18期
关键词
asynchronous generators; wind power plants; stators; wind turbines; damping; eigenvalues and eigenfunctions; machine control; control system synthesis; power system stability; power system oscillations; system electromechanical oscillations; doubly fed induction generator-based wind turbines; objective function; DFIG control gains; wind farm contribution; WF; system oscillation damping; DFIG stator mode; signal stability; dynamic stability; modified control design; additional damping; DFIG control design; DFIG-based wind turbines; INDUCTION GENERATOR; FARMS;
D O I
10.1049/joe.2018.9260
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Providing additional damping for system electromechanical oscillations through doubly fed induction generator (DFIG)-based wind turbines is investigated in this study. In this regard, first an objective function is developed to tune the DFIG control gains, aim to maximise the wind farm (WF) contribution to system oscillation damping, but it is shown that it causes a decrease in the damping of DFIG stator mode. In other words, with the current DFIG control design, it is not possible to improve both the small signal stability of the power system and the dynamic stability of WF together. Afterwards, two high-pass filters are suggested to be employed in the control design of DFIG. It is shown that with the modified control design, it is possible to improve the system oscillation without spoiling the dynamic stability of the WF itself. Eigenvalue analysis is performed to validate the effectiveness of the modified control design.
引用
收藏
页码:5330 / 5334
页数:5
相关论文
共 21 条
[1]  
Bianchi F.D., 2007, ADV IND CON
[2]   On Active/Reactive Power Modulation of DFIG-Based Wind Generation for Interarea Oscillation Damping [J].
Fan, Lingling ;
Yin, Haiping ;
Miao, Zhixin .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2011, 26 (02) :513-521
[3]   Modeling of DFIG-Based Wind Farms for SSR Analysis [J].
Fan, Lingling ;
Kavasseri, Rajesh ;
Miao, Zhixin Lee ;
Zhu, Chanxia .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2073-2082
[4]   Aggregated dynamic model for wind farms with doubly fed induction generator wind turbines [J].
Fernandez, Luis M. ;
Jurado, Francisco ;
Saenz, Jose Ramon .
RENEWABLE ENERGY, 2008, 33 (01) :129-140
[5]   Impact of Increased Penetration of DFIG-Based Wind Turbine Generators on Transient and Small Signal Stability of Power Systems [J].
Gautam, Durga ;
Vittal, Vijay ;
Harbour, Terry .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2009, 24 (03) :1426-1434
[6]   Control of DFIG-based wind generation for power network support [J].
Hughes, FM ;
Anaya-Lara, O ;
Jenkins, N ;
Strbac, G .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2005, 20 (04) :1958-1966
[7]   Interaction of the dynamics of doubly fed wind generators with power system electromechanical oscillations [J].
Jafarian, Mohammad ;
Ranjbar, Ali Mohammad .
IET RENEWABLE POWER GENERATION, 2013, 7 (02) :89-97
[8]  
Kundur P, 1994, POWER SYSTEM STABILI
[9]   Power oscillation damping supported by wind power: A review [J].
Luis Dominguez-Garcia, Jose ;
Gomis-Bellmunt, Oriol ;
Bianchi, Fernando D. ;
Sumper, Andreas .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2012, 16 (07) :4994-5006
[10]   Modal analysis of grid-connected doubly fed induction generators [J].
Mei, Francoise ;
Pal, Bikash .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2007, 22 (03) :728-736