Pollution performance of 110 kV metal oxide arresters

被引:9
作者
Chrzan, K
Pohl, Z
Grzybowski, S
Kohler, W
机构
[1] MISSISSIPPI STATE UNIV,DEPT ELECT & COMP ENGN,MISSISSIPPI STATE,MS 39762
[2] UNIV STUTTGART,DEPT ELECT ENGN,D-7000 STUTTGART,GERMANY
关键词
D O I
10.1109/61.584358
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Pollution test results of single unit 110 kV metal oxide surge arresters with porcelain housing according to the solid layer and salt Ibg methods are presented. During 6 hours of testing, the internal and external charge and maximum temperature along the varistor column were measured. The formation of single stable dry bands on the housing was often observed, especially during salt fog tests, In such cases, the varistor temperature can reach about 70 degrees C. The simple electrical model of the arrester enabling calculations of voltages and currents as a function of arrester and pollution parameters is shown.
引用
收藏
页码:728 / 733
页数:6
相关论文
共 7 条
[1]  
BARSCH R, 1991, PRUFUNG POLYMERKABEL, P1570
[2]  
CHRZAN K, 1995, 9 INT S HIGH VOLT EN
[3]  
DENIGRIS M, 1987, WORKSH POLL PERF INS
[4]  
FESER K, 1991, IEEE T POWER DEL APR, P688
[5]  
*IEC, 1994, IEC PUBL, V994
[6]  
Pilling J., 1993, 8 INT S HIGH VOLT EN
[7]  
VOSLOO WL, 1995, 9 INT S HIGH VOLT EN