Flow boiling heat transfer coefficient of R-134a/R-290/R-600a mixture in smooth horizontal tubes using varied heat flux method

被引:9
作者
Raja, B. [1 ]
Lal, D. Mohan [1 ]
Saravanan, R. [1 ]
机构
[1] Anna Univ, Coll Engn Guindy, Dept Mech Engn, R&AC Div, Madras 600025, Tamil Nadu, India
关键词
Refrigerant mixture; Flow boiling; Heat transfer coefficient; Stratified flow; Stratified-wavy; HC blend; Multiple regression; Correlation; GENERAL CORRELATION; 2-PHASE FLOW; REFRIGERANT MIXTURES; PATTERN; EVAPORATION; PURE; R22;
D O I
10.1016/j.applthermaleng.2008.08.009
中图分类号
O414.1 [热力学];
学科分类号
摘要
An experimental study on in-tube flow boiling heat transfer of R-134a/R-290/R-600a refrigerant mixture has been carried out under varied heat flux test conditions. The heat transfer coefficients are experimentally measured at temperatures between -8 and 5 degrees C for mass flow rates of 3-5 g s(-1). Acetone is used as a hot fluid which flows in the outer tube of diameter 28.57 mm while the refrigerant mixture flows in the inner tube of diameters 9.52 and 12.7 mm. By regulating the acetone flow conditions, the heat flux is maintained between 2 and 8 kW/m(2) and the pressure of the refrigerant is maintained between 3.2 and 5 bar. The comparison of experimental results with the familiar correlations shows that the correlations over predict the heat transfer coefficients for this mixture when stratified and stratified-wavy flow prevail. Multiple regression technique is used to evolve and modify existing correlations to predict the heat transfer coefficient of the refrigerant mixture. It is found that the modified version of Lavin-Young correlation (1965) predicts the heat transfer coefficient of the considered mixture within an average deviation of +/- 20.5%. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1778 / 1785
页数:8
相关论文
共 27 条
[1]   Experimental evaluation of R22 and R407C evaporative heat transfer coefficients in a vapour compression plant [J].
Aprea, C ;
de Rossi, F ;
Greco, A .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2000, 23 (05) :366-377
[2]   Two-phase heat transfer coefficients of three HFC refrigerants inside a horizontal smooth tube, part I: evaporation [J].
Boissieux, X ;
Heikal, MR ;
Johns, RA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2000, 23 (04) :269-283
[3]   CORRELATION FOR BOILING HEAT TRANSFER TO SATURATED FLUIDS IN CONVECTIVE FLOW [J].
CHEN, JC .
INDUSTRIAL & ENGINEERING CHEMISTRY PROCESS DESIGN AND DEVELOPMENT, 1966, 5 (03) :322-&
[4]   Performance and heat transfer characteristics of HFC-134a and CFC-12 in a water chiller [J].
Devotta, S ;
Parande, MG ;
Patwardhan, VR .
APPLIED THERMAL ENGINEERING, 1998, 18 (07) :569-578
[5]   COMPARATIVE-ASSESSMENT OF HFC134A AND SOME REFRIGERANTS AS ALTERNATIVES TO CFC12 [J].
DEVOTTA, S ;
GOPICHAND, S .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1992, 15 (02) :112-118
[6]   Evaporation of refrigerants in a smooth horizontal tube: prediction of R22 and R507 heat transfer coefficients and pressure drop [J].
Greco, A ;
Vanoli, GP .
APPLIED THERMAL ENGINEERING, 2004, 24 (14-15) :2189-2206
[7]  
GUNGOR KE, 1987, CHEM ENG RES DES, V65, P148
[8]   A GENERAL CORRELATION FOR FLOW BOILING IN TUBES AND ANNULI [J].
GUNGOR, KE ;
WINTERTON, RHS .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1986, 29 (03) :351-358
[9]  
Jabardo JMS, 2000, EXP THERM FLUID SCI, V23, P93
[10]   HORIZONTAL FLOW BOILING HEAT-TRANSFER EXPERIMENTS WITH A MIXTURE OF R22/R114 [J].
JUNG, DS ;
MCLINDEN, M ;
RADERMACHER, R ;
DIDION, D .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1989, 32 (01) :131-145