ADVANCED DISPATCHING OF A WIND FARM BASED ON DOUBLY FED INDUCTION GENERATORS FOR THE IMPROVEMENT OF LVRT CAPABILITY BY THE ADRC APPROACH

被引:0
|
作者
Laghridat, Hammadi [1 ]
Essadki, Ahmed [1 ]
Nasser, Tamou [2 ]
机构
[1] Mohammed V Univ, Higher Natl Sch Arts & Crafts, Elect Lab Res, Ave Nations Unies, Rabat 10106, Morocco
[2] Mohammed V Univ, Natl High Sch Comp Sci & Syst, Elect Lab Res, Ave Nations Unies, Rabat 10106, Morocco
关键词
Wind Farm; Wind Generator; Supervisory; DFIG; LVRT; ADRC; LOW-VOLTAGE RIDE; REACTIVE POWER; FAULT RIDE; THROUGH CAPABILITY; DFIG; ENHANCEMENT; TURBINES; PERFORMANCE; INTEGRATION; MANAGEMENT;
D O I
10.15598/aeee.v20i4.4411
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper aims to explore a viable monitoring and management of active and reactive powers for a large-scale wind farm based on Doubly -Fed Induction Generators (DFIG) considering the volt-age Fault-Ride-Through capability (FRT), especially Low-Voltage-Ride-Through (LVRT) capability by using a new control strategy, known as Active Disturbance Rejection Control. This strategy uses real-time estima-tion and compensation of the generalized "total" dis-turbance before it affects the system. The wind farm supervisory unit is used to coordinate the control of the powers production by the entire wind farm, which must take into account the couplings between each wind gen-erator while producing the individual power commands. The turbine control units (local supervisory units) send the appropriate power references depending on the sit-uation. This can be to produce the maximum power, to manage the active and reactive power given by the Transmission System Operator (TSO) or to meet the requirements of the grid code (LVRT capacity). How-ever, to ensure the dispatching of the references of the active and reactive powers over the all wind generators of the wind farm and to satisfy the security of the power grid, we utilized mean of the proportional distribution algorithm. The effectiveness of the proposed supervisory approach and control strategies are tested and vali-dated through a multiples scenarios of simulations that are made under the MATLAB/Simulink Environment. The results obtained have demonstrated the efficiency and robustness of the control methods, and also the fact that they guarantee good performance and safety of the integration of wind farms into the grid while complying with the requirements of the grid code during power system faults.
引用
收藏
页码:336 / 358
页数:23
相关论文
共 50 条
  • [41] DYNAMIC RESPONSE IMPROVEMENT OF DOUBLY FED INDUCTION GENERATOR-BASED WIND FARM USING FUZZY LOGIC CONTROLLER
    Hasanien, Hany M.
    Al-Ammar, Essam A.
    JOURNAL OF ELECTRICAL ENGINEERING-ELEKTROTECHNICKY CASOPIS, 2012, 63 (05): : 281 - 288
  • [42] Field tests and modelling of a wind form with doubly fed induction generators
    Meisingset, M
    Ohnstad, RM
    Uhlen, K
    Strand, LR
    WIND ENERGY, 2005, 8 (03) : 333 - 344
  • [43] Doubly fed induction generators for wind turbines - modeling the steady state
    Ofner, G.
    Handgruber, P.
    Seebacher, R.
    ELEKTROTECHNIK UND INFORMATIONSTECHNIK, 2011, 128 (05): : 174 - 180
  • [44] Mathematical Modelling of Grid Connected Doubly Fed Induction Generator Based Wind Farm
    Mahalakshmi, R.
    Viknesh, J.
    Thampatty, K. C. Sindhu
    2016 IEEE INTERNATIONAL CONFERENCE ON POWER ELECTRONICS, DRIVES AND ENERGY SYSTEMS (PEDES), 2016,
  • [45] Participation of doubly fed induction wind generators in system frequency regulation
    de Almeida, Rogerio G.
    Pecas Lopes, J. A.
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (03) : 944 - 950
  • [46] Fault Ride-Through Capability Improvement of Wind Farms Using Doubly Fed Induction Generator
    Karimi-Davijani, H.
    Sheikholeslami, A.
    Livani, H.
    Norouzi, N.
    2008 PROCEEDINGS OF THE 43RD INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE, VOLS 1-3, 2008, : 767 - 771
  • [47] Reactive power capability of a wind turbine with doubly fed induction generator
    Lund, Torsten
    Sorensen, Poul
    Eek, Jarle
    WIND ENERGY, 2007, 10 (04) : 379 - 394
  • [48] Noise-like-Signal-Based Sub-Synchronous Oscillation Prediction for a Wind Farm with Doubly-Fed Induction Generators
    Ma, Junjie
    Lyu, Linxing
    Man, Junfeng
    Chen, Mengqi
    Cheng, Yijun
    ELECTRONICS, 2024, 13 (11)
  • [49] Reactive Power Capability of the Wind Turbine with Doubly Fed Induction Generator
    Tian, J.
    Su, C.
    Chen, Z.
    39TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY (IECON 2013), 2013, : 5312 - 5317
  • [50] A novel approach for crowbar resistance determination for doubly fed induction generators in wind energy conversion systems
    Ibrahim, Nasseem Z.
    Al-Quteimat, Alaa
    Mozumdar, Mohmmad
    Al Jufout, Saleh
    INTERNATIONAL JOURNAL OF AMBIENT ENERGY, 2021, 43 (01) : 4102 - 4111