ADVANCED DISPATCHING OF A WIND FARM BASED ON DOUBLY FED INDUCTION GENERATORS FOR THE IMPROVEMENT OF LVRT CAPABILITY BY THE ADRC APPROACH

被引:0
|
作者
Laghridat, Hammadi [1 ]
Essadki, Ahmed [1 ]
Nasser, Tamou [2 ]
机构
[1] Mohammed V Univ, Higher Natl Sch Arts & Crafts, Elect Lab Res, Ave Nations Unies, Rabat 10106, Morocco
[2] Mohammed V Univ, Natl High Sch Comp Sci & Syst, Elect Lab Res, Ave Nations Unies, Rabat 10106, Morocco
关键词
Wind Farm; Wind Generator; Supervisory; DFIG; LVRT; ADRC; LOW-VOLTAGE RIDE; REACTIVE POWER; FAULT RIDE; THROUGH CAPABILITY; DFIG; ENHANCEMENT; TURBINES; PERFORMANCE; INTEGRATION; MANAGEMENT;
D O I
10.15598/aeee.v20i4.4411
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper aims to explore a viable monitoring and management of active and reactive powers for a large-scale wind farm based on Doubly -Fed Induction Generators (DFIG) considering the volt-age Fault-Ride-Through capability (FRT), especially Low-Voltage-Ride-Through (LVRT) capability by using a new control strategy, known as Active Disturbance Rejection Control. This strategy uses real-time estima-tion and compensation of the generalized "total" dis-turbance before it affects the system. The wind farm supervisory unit is used to coordinate the control of the powers production by the entire wind farm, which must take into account the couplings between each wind gen-erator while producing the individual power commands. The turbine control units (local supervisory units) send the appropriate power references depending on the sit-uation. This can be to produce the maximum power, to manage the active and reactive power given by the Transmission System Operator (TSO) or to meet the requirements of the grid code (LVRT capacity). How-ever, to ensure the dispatching of the references of the active and reactive powers over the all wind generators of the wind farm and to satisfy the security of the power grid, we utilized mean of the proportional distribution algorithm. The effectiveness of the proposed supervisory approach and control strategies are tested and vali-dated through a multiples scenarios of simulations that are made under the MATLAB/Simulink Environment. The results obtained have demonstrated the efficiency and robustness of the control methods, and also the fact that they guarantee good performance and safety of the integration of wind farms into the grid while complying with the requirements of the grid code during power system faults.
引用
收藏
页码:336 / 358
页数:23
相关论文
共 50 条
  • [31] Reactive power control of wind farm made up with doubly fed induction generators in distribution system
    Zhao, Jingjing
    Li, Xin
    Hao, Jutao
    Lu, Jiping
    ELECTRIC POWER SYSTEMS RESEARCH, 2010, 80 (06) : 698 - 706
  • [32] An elite approach for enhancement of LVRT in doubly fed induction generator (DFIG)-based wind energy conversion system (WECS): a FAMSANFIS approach
    Manohar, Gangikunta
    Venkateshwarlu, Sonnati
    JayaLaxmi, Askani
    SOFT COMPUTING, 2022, 26 (21) : 11315 - 11337
  • [33] Improved voltage control strategy of doubly-fed induction generators wind farm in distribution networks
    Zhang, Xue-Guang
    Liu, Yi-Cheng
    Hai, Ying
    Xu, Dian-Guo
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2010, 30 (07): : 29 - 35
  • [34] Application of ADRC in Variable-Speed Constant-Frequency Wind Energy Generation with Doubly-Fed Induction Generators
    Zhou Xuesong
    Li Chao
    Ma Youjie
    Li Ji
    Yu Yang
    PROCEEDINGS OF THE 29TH CHINESE CONTROL CONFERENCE, 2010, : 6061 - 6065
  • [35] Advanced Reactive Power Control Strategy for Better LVRT Capability for DFIG-based Wind Farm
    Gatavi, Ehsan
    Hellany, Ali
    Nagrial, Mahmood
    Rizk, Jamal
    2019 IEEE INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING AND 2019 IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS EUROPE (EEEIC / I&CPS EUROPE), 2019,
  • [36] Condition Assessment for Wind Turbines with Doubly Fed Induction Generators Based on SCADA Data
    Sun, Peng
    Li, Jian
    Wang, Caisheng
    Yan, Yonglong
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2017, 12 (02) : 689 - 700
  • [37] An overview on doubly fed induction generators' controls and contributions to wind based electricity generation
    Zin, Abdullah Asuhaimi B. Mohd
    Pesaran, Mahmoud H. A.
    Khairuddin, Azhar B.
    Jahanshaloo, Leila
    Shariati, Omid
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 27 : 692 - 708
  • [38] H∞ robust control for wind power systems based on doubly fed induction generators
    Fan, Pu-Cheng
    Wang, Chang-Song
    Wang, Zhi-Yu
    Yang, Jian-Cheng
    Beijing Keji Daxue Xuebao/Journal of University of Science and Technology Beijing, 2011, 33 (08): : 1018 - 1023
  • [39] Advanced control system of DFIG based wind generators for reactive power production and integration in a wind farm dispatching
    Ghennam, T.
    Aliouane, K.
    Akel, F.
    Francois, B.
    Berkouk, E. M.
    ENERGY CONVERSION AND MANAGEMENT, 2015, 105 : 240 - 250
  • [40] Transient Performance Improvement of Wind Turbines With Doubly Fed Induction Generators Using Nonlinear Control Strategy
    Rahimi, Mohsen
    Parniani, Mostafa
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2010, 25 (02) : 514 - 525