Three-phase photovoltaic generators modeling in unbalanced short-circuit operating conditions

被引:10
作者
Carpinelli, G. [2 ]
Bracale, A. [1 ]
Caramia, P. [1 ]
Di Fazio, A. R. [3 ]
机构
[1] Univ Napoli Parthenope, Dept Engn, Ctr Direz Napoli, Is C4, I-80143 Naples, Italy
[2] Univ Napoli Federico II, Dept Elect Engn & Informat Technol, Via Claudio 21, I-80125 Naples, Italy
[3] Univ Cassino & Southern Lazio, Dept Elect & Informat Engn, Via Biasio 43, I-03043 Cassino, FR, Italy
关键词
Short-circuit currents; Photovoltaic systems; Unbalanced power systems; Phase-coordinates approach; DISTRIBUTION-SYSTEMS; FAULT ANALYSIS; PROTECTION SCHEME; POWER-FLOW; WIND;
D O I
10.1016/j.ijepes.2019.06.011
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Photovoltaic systems (PVSs) are among the most diffuse Distributed Generators based on renewable energy sources. PVSs contribute to the short-circuit currents during a fault, modifying the short-circuit capacity of the distribution systems. Then, the contribution of PVSs to the fault current must be adequately modeled to extend the traditional short-circuit analysis to distribution networks with PVSs. In this paper an analytical model based on the phase-coordinates approach is proposed to evaluate the fault contributions of three-phase PVSs connected to unbalanced distribution networks in presence of symmetrical and asymmetrical shunt short-circuits, with and without fault impedance. The model of the PVS takes into account the environmental conditions, the inverter control system, the maximum current that can flow through the inverter switching devices, the filter, the interface transformer and the self-protections imposed by the Standard IEEE 1547. Both a first cycles and a steady-state model of the PVS are developed accounting for inverter control systems equipped with VAr or LVRT control schemes or inverter control system without reactive power regulation. The model of the PVS is applied to a typical North American MV network and the results of the proposed approach are compared with time-domain simulations.
引用
收藏
页码:941 / 951
页数:11
相关论文
共 35 条
[21]  
Nahman J., 1998, FACTA U SER ELECT EN, V11, P103
[22]  
Neumann T., 2012, IFAC Proc., V45, P343, DOI [10.3182/20120902-4-fr-2032.00061, DOI 10.3182/20120902-4-FR-2032.00061]
[23]   A Communication-Assisted Overcurrent Protection Scheme for Radial Distribution Systems With Distributed Generation [J].
Nikolaidis, Vassilis C. ;
Papanikolaou, Evangelos ;
Safigianni, Anastasia S. .
IEEE TRANSACTIONS ON SMART GRID, 2016, 7 (01) :114-123
[24]   Fault current contribution from synchronous machine and inverter based distributed generators [J].
Nimpitiwan, Natthaphob ;
Heydt, Gerald Thomas ;
Ayyanar, Raja ;
Suryanarayanan, Siddharth .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (01) :634-641
[25]   CORRELATION EQUATION FOR HOURLY DIFFUSE RADIATION ON A HORIZONTAL SURFACE [J].
ORGILL, JF ;
HOLLANDS, KGT .
SOLAR ENERGY, 1977, 19 (04) :357-359
[26]  
Plet C.A., 2010, POWER ENERGY SOC GEN, P1, DOI DOI 10.1109/PES.2010.5589981
[27]   Sequence Domain Calculation of Active Unbalanced Distribution Systems Affected by Complex Short Circuits [J].
Strezoski, Luka ;
Prica, Marija ;
Loparo, Kenneth A. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2018, 33 (02) :1891-1902
[28]   Generalized Δ-Circuit Concept for Integration of Distributed Generators in Online Short-Circuit Calculations [J].
Strezoski, Luka ;
Prica, Marija ;
Loparo, Kenneth A. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (04) :3237-3245
[29]  
Sutherland P., PRINCIPLES ELECT SAF, P299
[30]  