共 50 条
GRID CONNECTED HYBRID DISPERSED POWER GENERATORS BASED ON PV ARRAY AND WIND-DRIVEN INDUCTION GENERATOR
被引:0
|作者:
Arutchelvi, Meenakshisundaram
[1
]
Daniel, Samuel Arul
[2
]
机构:
[1] Saranathan Coll Engn, Fac Elect & Elect Engn, Tiruchirappalli, Tamil Nadu, India
[2] Natl Inst Technol, Fac Elect & Elect Engn, Tiruchirappalli 620015, Tamil Nadu, India
来源:
JOURNAL OF ELECTRICAL ENGINEERING-ELEKTROTECHNICKY CASOPIS
|
2009年
/
60卷
/
06期
关键词:
dispersed hybrid generators;
current control;
voltage source inverter;
wind-driven induction generator;
PV array;
VOLTAGE;
D O I:
暂无
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
A grid connected hybrid scheme for residential power supply based on an integrated photo-voltaic (PV) array and a wind-driven induction generator has been proposed in this paper. This new grid-connected configuration employs a closed loop controller at the inverter interfaced to the PV array to regulate the current fed to the grid. By varying the reference current to the controller the PV array meets the reactive power needs of the induction generator (IG) and also acts as a source of real power to the grid. A dynamic mathematical model of the hybrid scheme with variables expressed in d - q synchronous reference frame has been developed. The model is implemented in the Simpower (TM) platform, the simulation results bring out the usefulness of hybrid operation of PV, and wind-driven IG for grid connected operations.
引用
收藏
页码:313 / 320
页数:8