Design and operation of a tri-generation system for a station in China

被引:23
|
作者
Zhao, Xiling [1 ]
Fu, Lin [1 ]
Li, Feng [1 ]
Liu, Hua [1 ]
机构
[1] Tsinghua Univ, Sch Architecture, Dept Bldg Sci, Beijing 100084, Peoples R China
关键词
Tr-generation; Absorption heat pump; Condensation heat recovery; Energy and exergy analysis C-cw; CHP SYSTEMS; TRIGENERATION; POWER;
D O I
10.1016/j.enconman.2014.01.019
中图分类号
O414.1 [热力学];
学科分类号
摘要
Tr-generation usually refers to the simultaneous production of power, heating and cooling. Tri-generation can be regarded as a high-efficiency technology, provided that a large proportion of the energy rejected by the prime mover is used. In this paper, the design and operation of a tri-generation system for a railway station was investigated. The system is composed of the internal combustion engine (ICE), absorption heat pump (AHP), heat exchanger (HE), and other facilities. The system was built and operated in 2011, and the energy efficiency level was analyzed. The results indicated that the calculated maximum comprehensive energy efficiency (CEE) was 94.94% in the winter and 84.33% in the summer; with the calculated maximum exergy efficiency is 38.01% in the winter and 36.01% in the summer. The primary energy saving (PES) of the system was 32.2% in the winter and 4.9% in the summer. The system could therefore be regarded as high efficiency tri-generation. The recovered year of the increased investment was 5.47 year compared with the reference system. These results could serve as a reference for designing or evaluating tri-generation systems. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:391 / 397
页数:7
相关论文
共 50 条
  • [1] Design and optimisation of a small-scale tri-generation system
    Boukhanouf, R.
    Godefroy, J.
    Riffat, S. B.
    Worall, M.
    INTERNATIONAL JOURNAL OF LOW-CARBON TECHNOLOGIES, 2008, 3 (01) : 32 - 43
  • [2] A tri-generation electrogasdynamic ejection system
    Riffat, SB
    Su, YH
    JOURNAL OF THE ENERGY INSTITUTE, 2004, 77 (510) : 7 - 10
  • [3] Operation Strategy and Parametric Analysis of a CHP and a Tri-Generation System for Integrated Community
    Choi, Junwon
    Yun, Rin
    INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2015, 23 (01)
  • [4] Design Modeling and System Integration of Fuel Cell in Tri-Generation System-Review
    Hasarmani, T. S.
    Holmukhe, R. M.
    Bankar, D. S.
    INTERNATIONAL CONFERENCE ON SUSTAINABLE ENGINEERING AND TECHNOLOGY (ICONSET 2018), 2018, 2039
  • [5] Production of ice water in a tri-generation centralized system
    Schroeder, Andrzej
    Lach, Jan
    Poskrobko, Slawomir
    Archives of Thermodynamics, 2007, 28 (04) : 41 - 62
  • [6] Performance evaluation of a tri-generation system with simulation and experiment
    Ge, Y. T.
    Tassou, S. A.
    Chaer, I.
    Suguartha, N.
    APPLIED ENERGY, 2009, 86 (11) : 2317 - 2326
  • [7] Experimental and computational investigation for a household tri-generation with HES system
    Chen, Xiangping
    Liu, Yilin
    Yuan, Xufeng
    Wu, Qinmu
    Li, Zetao
    2017 9TH INTERNATIONAL CONFERENCE ON MODELLING, IDENTIFICATION AND CONTROL (ICMIC 2017), 2017, : 1014 - 1019
  • [8] Analysis of tri-generation system in combined cooling and heating mode
    Wang, Jialong
    Wu, Jingyi
    Zheng, Chunyuan
    ENERGY AND BUILDINGS, 2014, 72 : 353 - 360
  • [9] Optimisation studies on tri-generation: a review
    Unal, Ali Nadi
    Ercan, Secil
    Kayakutlu, Gulgun
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2015, 39 (10) : 1311 - 1334
  • [10] Design and dynamics simulations of small scale solid oxide fuel cell tri-generation system
    Wu, Chien-Chang
    Chen, Tsung-Lin
    ENERGY CONVERSION AND MANAGEMENT-X, 2019, 1