A Non-Standard Characteristic Based Protection Scheme for Distribution Networks

被引:17
作者
Kilickiran, Hasan Can [1 ,2 ]
Akdemir, Huseyin [1 ]
Sengor, Ibrahim [1 ]
Kekezoglu, Bedri [1 ]
Paterakis, Nikolaos G. [2 ]
机构
[1] Yildiz Tech Univ, Dept Elect Engn, Davutpasa Campus, TR-34220 Istanbul, Turkey
[2] Eindhoven Univ Technol TU E, Dept Elect Engn, POB 513, NL-5600 MB Eindhoven, Netherlands
关键词
digital relay; non-standard characteristic; non-standard curve; protection; unconventional relay characteristic; OVERCURRENT RELAYS; DISTRIBUTION-SYSTEMS; COORDINATION; GENERATION;
D O I
10.3390/en11051241
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The increasing number of distributed generation (DG) units in the distribution systems poses a challenge on protection systems in terms of coordination. In addition, the single characteristic based conventional protection causes an increase in the primary operation time of the relays due to the coordination between relay pairs. As a consequence, earlier studies investigated the utilization of non-standard characteristics and protection schemes in order to ease the insufficiencies of the standard approach. However, a commonly accepted protection approach that mitigates the effect of DG while providing lower primary operating time by levering the benefits of the non-standard protection strategy has not been developed so far. In order to overcome the aforementioned drawbacks of traditional protection, this paper firstly introduces a non-standard characteristic and then proffers an unconventional protection strategy, which utilizes a double characteristic. The suggested protection approach is tested on the IEEE 14 Bus distribution system including synchronous generator based DG connection. The results show that the proposed characteristic and protection scheme are able to provide a substantial decrease in the operation time of the relays while meeting the coordination requirements.
引用
收藏
页数:13
相关论文
共 29 条
[1]   Design and implementation of a multifunction DSP-based-numerical relay [J].
Abdel-Salam, Mazen ;
Kamel, Rashad ;
Sayed, Khairy ;
Khalaf, Mohsen .
ELECTRIC POWER SYSTEMS RESEARCH, 2017, 143 :32-43
[2]  
Aghdam TS, 2017, INT J RENEW ENERGY R, V7, P636
[3]   Application of hyper-spherical search algorithm for optimal coordination of overcurrent relays considering different relay characteristics [J].
Ahmadi, S. A. ;
Karami, H. ;
Sanjari, M. J. ;
Tarimoradi, H. ;
Gharehpetian, G. B. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2016, 83 :443-449
[4]  
Alkaran D. S., 2016, IEEE T SMART GRID
[5]  
Anderson P.M., 1998, Power System Protection
[6]  
[Anonymous], 2009, COMPUTER RELAYING PO
[7]  
[Anonymous], DIGSILENT POWERFACTO
[8]   Overcurrent relay with unconventional curves and its application in industrial power systems [J].
Arreola Soria, O. ;
Conde Enriquez, A. ;
Trujillo Guajardo, L. A. .
ELECTRIC POWER SYSTEMS RESEARCH, 2014, 110 :113-121
[9]   Development of adaptive protection scheme for distribution systems with high penetration of distributed generation [J].
Brahma, SM ;
Girgis, AA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :56-63
[10]   Fold back current control and admittance protection scheme for a distribution network containing distributed generators [J].
Dewadasa, M. ;
Ghosh, A. ;
Ledwich, G. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2010, 4 (08) :952-962