Ability of transfer function method to diagnose axial displacement of transformer windings

被引:0
|
作者
Rahimpour, E [1 ]
Christian, J [1 ]
Feser, K [1 ]
Mohseni, H [1 ]
机构
[1] Univ Stuttgart, Int Power Transmiss & High Voltage Technol, D-70569 Stuttgart, Germany
来源
关键词
D O I
10.1002/etep.4450120309
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Transient currents can cause the mechanical displacement of transformer windings. The transfer function method is presented as a tool to detect this displacement. hi order to be able to evaluate the measurements, the correlation between the characteristics of transfer functions and possible damages must be known. Axial displacement of transformer windings has been studied in this research. As test object a transformer with a primary winding of 31 double inverted disk (approx. 1.3 MVA, 10 kV) and a secondary winding with four layer concentric winding was used. A detailed mathematical model was developed for the test object and a comparison was carried out between measured and calculated results. To compare the sensitivity of transfer functions, five different transfer functions with different terminal conditions are simulated. It is shown that the detailed model can present the behaviour of the transformer winding in case of sound and displaced windings.
引用
收藏
页码:225 / 233
页数:9
相关论文
共 50 条
  • [1] Transfer function method to diagnose axial displacement and radial deformation of transformer windings
    Rahimpour, E
    Christian, J
    Feser, K
    Mohseni, H
    IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (02) : 493 - 505
  • [2] Ability of detailed model to diagnose axial displacement of transformer windings
    Rahimpour, E
    Christian, J
    Feser, K
    Mohseni, H
    ELECTRICAL ENGINEERING, 2001, 83 (1-2) : 55 - 61
  • [3] Ability of detailed model to diagnose axial displacement of transformer windings [Die Fähigkeit eines detaillierten Modells zur Diagnose axialer Verschiebungen in Transformatorwicklungen mit Hilfe von Übertragungsfunktionen]
    Rahimpour E.
    Christian J.
    Feser K.
    Mohseni H.
    Electrical Engineering, 2001, 83 (1-2) : 55 - 61
  • [4] The effects of axial displacement of transformer windings on impulse and transferred voltage distribution
    Rahimpour, E
    Hamidi, N
    ELECTRIC POWER SYSTEMS RESEARCH, 2006, 76 (6-7) : 509 - 514
  • [5] Diagnostics of Transformer Windings Deformation Based on Transfer Function
    Yin, Lei
    Wu, Zhensheng
    Gui, Junfeng
    PROCEEDINGS OF THE 2013 INTERNATIONAL CONFERENCE ON ELECTRICAL AND INFORMATION TECHNOLOGIES FOR RAIL TRANSPORTATION (EITRT2013), VOL II, 2014, 288 : 65 - 72
  • [6] Estimation of simulated transfer function to discriminate axial displacement and radial deformation of transformer winding
    Karimifard, Peyman
    Gharehpetian, G. B.
    Ghanizadeh, Ahmad Javid
    Tenbohlen, Stefan
    COMPEL-THE INTERNATIONAL JOURNAL FOR COMPUTATION AND MATHEMATICS IN ELECTRICAL AND ELECTRONIC ENGINEERING, 2012, 31 (04) : 1277 - 1292
  • [7] Determination of axial displacement extent based on transformer winding transfer function estimation using vector-fitting method
    Karimifard, P.
    Gharehpetian, G. B.
    Tenbohlen, S.
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2008, 18 (04): : 423 - 436
  • [8] DYNAMIC AXIAL FORCES IN TRANSFORMER WINDINGS
    LURE, SI
    SAVELEV, MP
    ELECTRICAL TECHNOLOGY, 1972, 2 : 101 - 120
  • [9] Modeling of the transformer windings under VFTO based on transfer function
    Zhang, Xile
    Liang, Guishu
    Xie, Qing
    Sun, Haifeng
    2006 INTERNATIONAL CONFERENCE ON POWER SYSTEMS TECHNOLOGY: POWERCON, VOLS 1- 6, 2006, : 1704 - +
  • [10] Transfer Function Based Recognition of Resonance Overvoltages in Transformer Windings
    Florkowski, M.
    Furgal, J.
    ICHVE 2008: 2008 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION, 2008, : 12 - +