Analysis and optimization of CCHP systems based on energy, economical, and environmental considerations

被引:311
作者
Mago, P. J. [1 ]
Chamra, L. M. [1 ]
机构
[1] Mississippi State Univ, Dept Mech Engn, Mississippi State, MS 39762 USA
关键词
CCHP systems; Operation strategies; Primary energy; Emissions reduction; TRIGENERATION; POWER; COGENERATION; PERFORMANCE; METHODOLOGY; COST;
D O I
10.1016/j.enbuild.2009.05.014
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Analysis of combined cooling, heating, and power (CCHP) systems is frequently based on reduction of operating cost without measuring the actual energy use and emissions reduction. CCHP systems can be optimized based on different optimization criterion such as: energy savings, operation cost reduction or minimum environmental impact. In this study, CCHP systems operated following the electric load (FEL) and the thermal load (FTL) strategies are evaluated and optimized based on: primary energy consumption (PEC), operation cost, and carbon dioxide emissions (CDE). This study also includes the analysis and evaluation of an optimized operational strategy in which a CCHP system follows a hybrid electric-thermal load (HETS) during its operation. Results show that CCHP systems operating using any of the optimization criteria have better performance than CCHP systems operating without any optimization criteria. For the evaluated city, the optimum PEC and cost reduction are 7.5% and 4.4%, respectively, for CCHP-FTL, while the optimum CDE reduction is 14.8% for CCHP-FEL. Results also show that the HETS is a good alternative for CCHP systems operation since it gives good reduction of PEC, cost, and CDE. This optimized operation strategy provides a good balance among all the variables considered in this paper. (C) 2009 Elsevier B.V. All rights reserved.
引用
收藏
页码:1099 / 1106
页数:8
相关论文
共 21 条
[1]   A new approach to exergoeconomic analysis and design of variable demand energy systems [J].
Cardona, E ;
Piacentino, A .
ENERGY, 2006, 31 (04) :490-515
[2]   A validation methodology for a combined heating cooling and power (CHCP) pilot plant [J].
Cardona, E ;
Piacentino, A .
JOURNAL OF ENERGY RESOURCES TECHNOLOGY-TRANSACTIONS OF THE ASME, 2004, 126 (04) :285-292
[3]   A methodology for sizing a trigeneration plant in mediterranean areas [J].
Cardona, E ;
Piacentino, A .
APPLIED THERMAL ENGINEERING, 2003, 23 (13) :1665-1680
[4]   From cogeneration to trigeneration: Profitable alternatives in a competitive market [J].
Chicco, G ;
Mancarella, P .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2006, 21 (01) :265-272
[5]   Assessment of the greenhouse gas emissions from cogeneration and trigeneration systems. Part I: Models and indicators [J].
Chicco, Gianfranco ;
Mancarella, Pierluigi .
ENERGY, 2008, 33 (03) :410-417
[6]   Distributed multi-generation: A comprehensive view [J].
Chicco, Gianfranco ;
Mancarefla, Pierluigi .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2009, 13 (03) :535-551
[7]  
EnergyPlus, EN SIM SOFTW
[8]   Cooling, heating, and power energy performance for system feasibility [J].
Fumo, N. ;
Mago, P. J. ;
Chamra, L. M. .
PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART A-JOURNAL OF POWER AND ENERGY, 2008, 222 (A4) :347-354
[9]  
Jalalzadeh-Azar A.A., 2004, ASHRAE T, P85
[10]   Energy utilization evaluation of CCHP systems [J].
Li, H ;
Fu, L ;
Geng, KC ;
Jiang, Y .
ENERGY AND BUILDINGS, 2006, 38 (03) :253-257