Study on the dynamic and thermal performances of a reversibly used cooling tower with upward spraying

被引:36
作者
Cui, Haijiao [1 ]
Li, Nianping [1 ]
Peng, Jinqing [1 ]
Cheng, Jianlin [1 ]
Li, Shengbing [1 ]
机构
[1] Hunan Univ, Coll Civil Engn, Changsha 410081, Hunan, Peoples R China
基金
中国国家自然科学基金;
关键词
Reversibly used cooling towers; Upward spraying; Heat pumps; Droplet dynamics; Thermal performance; Heat and mass transfer; MASS-TRANSFER; NUMERICAL-ANALYSIS; PARTICLE COLLECTION; HEATING-SYSTEM; AIR; SIMULATION; DIFFUSIOPHORESIS; DROPLETS; RUWCT;
D O I
10.1016/j.energy.2015.12.065
中图分类号
O414.1 [热力学];
学科分类号
摘要
In subtropical areas, the RUCT (reversibly used cooling tower) can be used in a heat pump system. This study proposed an upward spraying RUCT, in which the aqueous solution is sprayed upward from the bottom, to reduce the drag resistance and enhance the efficiency of conventional RUCTs. A mathematical model considering rising and falling droplets simultaneously was developed based on conversation laws of mass, energy and momentum. The validity of the model was examined against the operating data measured in real conditions. Based on the validated model, the influences of different air velocities (2, 2.5, 3 m/s), droplet diameters (0.8, 1.0, 1.2 mm) and initial droplet velocities (6, 8, 10 m/s) on the displacement, velocity and temperature distributions of the sprayed droplet were discussed in detail. The results showed that, when the ratio of initial droplet velocity to air velocity closes to 1, smaller droplets will rise higher than the larger droplets, while for large ratio, the opposite is true. Droplet diameter had a large impact on the thermal performance and the droplet temperature rise in the descent stage was 1.5 2.4 times larger than that in the ascent stage. This study provides a theoretical foundation for optimization designing of the upward spraying RUCT. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:268 / 277
页数:10
相关论文
共 42 条
[21]   Experimental investigation of the hydraulic characteristics of a counter flow wet cooling tower [J].
Lemouari, M. ;
Boumaza, M. ;
Kaabi, A. .
ENERGY, 2011, 36 (10) :5815-5823
[22]   Experimental analysis of heat and mass transfer phenomena in a direct contact evaporative cooling tower [J].
Lemouari, M. ;
Boumaza, M. ;
Kaabi, A. .
ENERGY CONVERSION AND MANAGEMENT, 2009, 50 (06) :1610-1617
[23]   Innovative correlation for calculating thermal performance of counterflow wet-cooling tower [J].
Mansour, M. Khamis ;
Hassab, M. A. .
ENERGY, 2014, 74 :855-862
[24]   Performance characteristics of a downward spray water-jet cooling tower [J].
Muangnoi, Thirapong ;
Asvapoositkul, Wanchai ;
Hungspreugs, Pibool .
APPLIED THERMAL ENGINEERING, 2014, 69 (1-2) :165-176
[25]   Performance analysis of a low approach low temperature direct cooling tower for high-temperature building cooling systems [J].
Nasrabadi, Mehdi ;
Finn, Donal P. .
ENERGY AND BUILDINGS, 2014, 84 :674-689
[26]   Numerical analysis on performance enhancement of a CO2 heat pump water heating system by extracting tepid water [J].
Ohkura, Masashi ;
Yokoyama, Ryohei ;
Nakamata, Takuya ;
Wakui, Tetsuya .
ENERGY, 2015, 87 :435-447
[27]   CALCULATED PARTICLE COLLECTION EFFICIENCIES OF SINGLE DROPLETS INCLUDING INERTIAL IMPACTION, BROWNIAN DIFFUSION, DIFFUSIOPHORESIS AND THERMOPHORESIS [J].
PILAT, MJ ;
PREM, A .
ATMOSPHERIC ENVIRONMENT, 1976, 10 (01) :13-19
[28]   Numerical simulation of shower cooling tower based on artificial neural network [J].
Qi, Xiaoni ;
Liu, Zhenyan ;
Li, Dandan .
ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (04) :724-732
[29]   Further investigation on the performance of a shower cooling tower [J].
Qi, Xiaoni ;
Liu, Zhenyan .
ENERGY CONVERSION AND MANAGEMENT, 2008, 49 (04) :570-577
[30]   Performance characteristics of a shower cooling tower [J].
Qi, Xiaoni ;
Liu, Zhenyan ;
Li, Dandan .
ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (01) :193-203