Condition assessment of contacts in gas-insulated substations

被引:22
|
作者
Runde, M [1 ]
Lillevik, O
Larsen, V
Skyberg, B
Mjelve, A
Tonstad, A
机构
[1] Norwegian Univ Sci & Technol, N-7034 Trondheim, Norway
[2] SINTEF, Energy Res, N-7034 Trondheim, Norway
[3] TransiNor, Trondheim, Norway
[4] Statnett, Oslo, Norway
[5] Viken Nett, Oslo, Norway
[6] Sira Kvina Kraftselskap, Tonstad, Norway
关键词
contact resistance; contacts; fault diagnosis; gas-insulated substations; test equipment; testing;
D O I
10.1109/TPWRD.2003.822942
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A new method for assessing the condition of electric contacts and joints inside gas-insulated substations (GISs) that overcomes the limitations of conventional diagnostic methods is proposed. The contact resistance in degraded or overstressed electrical contacts varies slightly when currents of different amplitudes are passed. The diagnostic method is based on detecting this nonlinear behavior. For testing of the contacts in large GIS, excitation currents up to several thousand amperes are required. By using a capacitor-based current supply, such currents can be achieved with a portable source. The testing can be carried out without dismantling the GIS. No earlier measurements or manufacturer specifications are required. In full-scale testing under realistic operating conditions on 145-420 kV GIS using prototype instrumentation a very good sensitivity for detecting contact degradation in an early stage was obtained.
引用
收藏
页码:609 / 617
页数:9
相关论文
共 50 条
  • [1] GAS-INSULATED AND HYBRID SUBSTATIONS
    Ruiz Flores, Luis Ivan
    Hernandez Munoz, Nestor A.
    Salazar Castro, Israel
    Martinez Torres, Valentin
    IEEE INDUSTRY APPLICATIONS MAGAZINE, 2014, 20 (05) : 64 - 70
  • [2] Overvoltage protection of gas-insulated substations
    Simms, J.R.
    GEC Review, 1988, 4 (02): : 100 - 108
  • [3] DIAGNOSTIC METHODS FOR GAS-INSULATED SUBSTATIONS
    TAKAHASHI, Y
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1986, 21 (06): : 1037 - 1043
  • [4] EXPERIENCE WITH GAS-INSULATED SUBSTATIONS IN THE USA
    ERIKSSON, A
    PETTERSSON, KG
    KRENICKY, A
    BAKER, R
    OCHOA, JR
    LEIBOLD, A
    BOLIN, PC
    BOGGS, SA
    IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (01) : 210 - 218
  • [5] GAS-INSULATED SUBSTATIONS FAULT SURVEY
    CHU, FY
    TAHILIANI, V
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (06): : 2351 - 2356
  • [6] Addendum I to bibliography of gas-insulated substations
    Anon
    IEEE Transactions on Power Delivery, 1992, v (0n) : 1003 - 1020
  • [7] A CONTINUOUS UHF MONITOR FOR GAS-INSULATED SUBSTATIONS
    PEARSON, JS
    HAMPTON, BF
    SELLARS, AG
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1991, 26 (03): : 469 - 478
  • [8] PARTIAL DISCHARGE DIAGNOSTICS FOR GAS-INSULATED SUBSTATIONS
    PEARSON, JS
    FARISH, O
    HAMPTON, BF
    JUDD, MD
    TEMPLETON, D
    PRYOR, BM
    WELCH, IM
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1995, 2 (05) : 893 - 905
  • [9] DIAGNOSTIC METHODS FOR GAS-INSULATED SUBSTATIONS.
    Takahashi, Y.
    IEEE transactions on electrical insulation, 1986, EI-21 (06): : 1037 - 1043