Strategic placements of PMUs for power network observability considering redundancy measurement

被引:35
作者
Babu, Rohit [1 ]
Bhattacharyya, Biplab [1 ]
机构
[1] Indian Sch Mines, Indian Inst Technol, Dept Elect Engn, Dhanbad 826004, Jharkhand, India
关键词
Binary integer linear programming; Branch-and-bound; Interconnected power network; Mixed-integer nonlinear programming; Measurement redundancy; Optimal PMU placement; Observability analysis; Phasor measurement unit; Two-phase branch-and-bound algorithm; PHASOR MEASUREMENT UNITS;
D O I
10.1016/j.measurement.2018.11.001
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper proposes a mixed integer nonlinear programming (MINLP) formulation with binary-valued variables for the optimal installation of the phasor measurement units (PMUs) in a power network. The MINLP framework has been solved by a two-phase branch-and-bound algorithm (BBA) for the optimal PMU placement (OPP) problem. The present work deals with the solution of the OPP problem without considering the radial buses including in the optimal solution. PMU is pre-assigned to each bus connected to a radial bus such that the radial buses are excluded from the list of potential PMU locations. The programming technique is used to determine the optimum number of PMUs and their locations to make the interconnected power network completely observable. The proposed BBA may provide multiple solutions at the lowest objective value, each time the optimizer routine restarts. Therefore, the obtained optimal solutions are being ranked regarding the measurement redundancy index. The two-phase branch-and-bound algorithm is applied to IEEE standard test systems as well as to New England 39-bus and a northern regional power grid 246-bus system. The proposed algorithm has been compared with the existing programming techniques in the recent literature. The simulation results obtained by the proposed BBA indicate the effectiveness and the efficiency to detect the desired target. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:606 / 623
页数:18
相关论文
共 48 条
[1]  
Abur A., 2004, Power System State Estimation Theory andImplementation
[2]  
[Anonymous], 1986, IEEE POWER ENG REV
[3]  
[Anonymous], STATE ESTIMATION ELE
[4]  
[Anonymous], 2010, INTRO NONLINEAR GLOB
[5]  
Arora J.S., 2004, Introduction to Optimum Design
[6]  
Arora RajeshKumar., 2019, Optimization: algorithms and applications
[7]  
Babu R, 2017, INT J EMERG ELECTR P, V18, DOI 10.1515/ijeeps-2017-0073
[8]   Optimal allocation of phasor measurement unit for full observability of the connected power network [J].
Babu, Rohit ;
Bhattacharyya, Biplab .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2016, 79 :89-97
[9]   POWER-SYSTEM OBSERVABILITY WITH MINIMAL PHASOR MEASUREMENT PLACEMENT [J].
BALDWIN, TL ;
MILI, L ;
BOISEN, MB ;
ADAPA, R .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (02) :707-715
[10]   Optimal placement of phasor measurement units for power system observability [J].
Chakrabarti, Saikat ;
Kyriakides, Elias .