Adaptive VDCOL control strategy for the recovery of the UHVDC SPC system

被引:5
作者
Yao, Shujun [1 ]
Huang, Wenerda [1 ]
Hao, Wenbo [2 ]
Guo Wanhua [1 ]
机构
[1] North China Elect Power Univ, Sch Elect & Elect Engn, Beijing, Peoples R China
[2] Heilongjiang Elect Power Res Inst, Harbin, Heilongjiang, Peoples R China
来源
JOURNAL OF ENGINEERING-JOE | 2019年 / 16期
关键词
voltage control; power transmission control; HVDC power transmission; commutation; reactive power control; power system stability; power system interconnection; power transmission reliability; adaptive VDCOL control strategy; UHVDC SPC system; ultra-high-voltage direct current; power stability; receiving systems; subsequent commutation failure; adaptive voltage-dependent; VDCOL characteristics; low-voltage situations; simulation systems; SPC mode; voltage level; pole connection mode; AC-]DC interconnection system; voltage; 800; 0; kV;
D O I
10.1049/joe.2018.8759
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The separating pole connection (SPC) mode of ultra-high-voltage direct current (UHVDC) can significantly improve the power stability, but when the AC bus of one pole is failed and two receiving systems are near, it may cause subsequent commutation failure. In order to restrain subsequent commutation failure and accelerate system's recovery, an adaptive voltage-dependent current order limiter (VDCOL) control strategy based on granular computing is proposed. According to this VDCOL control strategy, VDCOL, which uses fuzzy rules to separate and granulate a different voltage level, can adjust DC current dynamically in a variety of environments. Also, some modifications on VDCOL characteristics are applied to reduce reactive power consumption during low-voltage situations. Then based on the MATLAB simulation platform, the simulation systems for 800kV the UHVDC SPC system are built. Finally, the simulation example of the SPC mode with the adaptive VDCOL control strategy showed that this VDCOL control strategy can reduce the risk of subsequent commutation failure and improve the stability of the AC/DC interconnection system.
引用
收藏
页码:1754 / 1758
页数:5
相关论文
共 11 条
[1]  
[Anonymous], P AS PAC POW EN ENG
[2]  
[Anonymous], 2008, B441 CIGRE WORK GROU
[3]  
Juanjuan W, 2008, ELECT POWER AUTOM EQ, V32, P16
[4]  
Ke W., 2007, JIANGSU ELECT ENG, V26, P1
[5]  
[刘磊 Liu Lei], 2015, [电网技术, Power System Technology], V39, P1814
[6]   Hierarchical Clustering Problems and Analysis of Fuzzy Proximity Relation on Granular Space [J].
Tang, Xu-Qing ;
Zhu, Ping .
IEEE TRANSACTIONS ON FUZZY SYSTEMS, 2013, 21 (05) :814-824
[7]  
Vojislav K., 2001, Learning and Soft Computing- Support Vector Machines, Neural Networks and Fuzzy Logic Models
[8]  
Wang J, 2016, ASIA-PAC POWER ENERG, P1023, DOI 10.1109/APPEEC.2016.7779651
[9]   Granular Computing and Knowledge Reduction in Formal Contexts [J].
Wu, Wei-Zhi ;
Leung, Yee ;
Mi, Ju-Sheng .
IEEE TRANSACTIONS ON KNOWLEDGE AND DATA ENGINEERING, 2009, 21 (10) :1461-1474
[10]   分极接入模式的多端直流特点与故障响应比较 [J].
张东辉 ;
金小明 ;
洪潮 ;
徐光虎 ;
吴林平 ;
邵震霞 ;
王俊生 ;
柏传军 .
南方电网技术, 2015, 9 (11) :25-30