Optimum design of cooling water systems for energy and water conservation

被引:82
作者
Panjeshahi, M. H. [1 ]
Ataei, A. [2 ]
Gharaie, M. [3 ]
Parand, R. [3 ]
机构
[1] Univ Tehran, Dept Chem Engn, Tehran, Iran
[2] Azad Univ, Environm & Energy Dept, Tehran, Iran
[3] KN Toosi Univ Technol, Dept Mech Engn, Tehran, Iran
关键词
Re-circulating cooling water system; Cooling tower; Pinch technology; Mathematical programming; Ozone treatment; Water-energy conservation;
D O I
10.1016/j.cherd.2008.08.004
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
Re-circulating cooling water systems (RCWSs) are widely used to reject waste process heat to the environment, conserve fresh water and reduce thermal pollution relative to once-through systems. Research on RCWS has mostly focused on individual components, cooling tower and heat-exchanger network. Kim and Smith [Kim, J.K. and Smith, R., 2001, Cooling water system design, Chem Eng Sci, 56(12): 3641-3658] developed a grass-root design method of RCWS (KSD). In this paper, the KSD method is expanded and a comprehensive simulation model of RCWS is developed accounting for interaction between cooling tower and heat-exchanger network. Regarding this model, a modern grass-root design method of RCWS, we call it Advanced Pinch Design (APD), based on combined pinch technology and mathematical programming is developed for minimum cost achievement. Having considered cycle water quality through introducing ozone treatment technology, APD methodology is further improved. This technique that we call Enhanced Cooling Water System Design (ECWSD), as the APD supplementary methodology, is provided water and energy conservation, minimum cost and environmental impacts. Related coding in MATLAB version 7.1 is developed for the illustrative example to get optimal values in RCWS design method computations. Finally the results of the introduced grass-root design methodologies, APD and ECWSD, are compared with KSD. Crown Copyright (C) 2008 Published by Elsevier B.V. on behalf of The Institution of Chemical Engineers. All rights reserved.
引用
收藏
页码:200 / 209
页数:10
相关论文
共 16 条
  • [1] Optimisation of ozone production for water and wastewater treatment
    Alsheyab, Mohammad A. T.
    Munoz, Aurelio H.
    [J]. DESALINATION, 2007, 217 (1-3) : 1 - 7
  • [2] Operational cost minimization in cooling water systems
    Castro, MM
    Song, TW
    Pinto, JM
    [J]. BRAZILIAN JOURNAL OF CHEMICAL ENGINEERING, 2000, 17 (4-7) : 649 - 658
  • [3] Coulson J.M., 1996, Chemical engineering: Fluid flow, heat transfer and mass transfer, V5th
  • [4] GHARAIE M, 2007, THESIS KN TOOSI U TE
  • [5] Cooling water system design
    Kim, JK
    Smith, R
    [J]. CHEMICAL ENGINEERING SCIENCE, 2001, 56 (12) : 3641 - 3658
  • [6] Design of cooling systems for effluent temperature reduction
    Kim, JK
    Savulescu, L
    Smith, R
    [J]. CHEMICAL ENGINEERING SCIENCE, 2001, 56 (05) : 1811 - 1830
  • [7] KROGER DG, 2004, AIR COOLED HEAT EXCH, P223
  • [8] Effluent treatment system design
    Kuo, WCJ
    Smith, R
    [J]. CHEMICAL ENGINEERING SCIENCE, 1997, 52 (23) : 4273 - 4290
  • [9] Mann J.G., 1999, Industrial water reuse and wastewater minimization
  • [10] A comprehensive approach to cooling tower design
    Milosavljevic, N
    Heikkilä, P
    [J]. APPLIED THERMAL ENGINEERING, 2001, 21 (09) : 899 - 915