Numerical simulation and performance improvement for a small size shell-and-tube heat exchanger with trefoil-hole baffles

被引:37
作者
You, Yonghua [1 ,2 ]
Chen, Yuqi [1 ]
Xie, Mengqian [1 ]
Luo, Xiaobing [3 ]
Jiao, Lan [4 ]
Huang, Suyi [3 ]
机构
[1] Wuhan Univ Sci & Technol, State Key Lab Refractories & Met, Wuhan 430081, Peoples R China
[2] Wuhan Univ Sci & Technol, Minist Educ, Key Lab Ferrous Met & Resources Utilizat, Wuhan 430081, Peoples R China
[3] Huazhong Univ Sci & Technol, Sch Energy & Power Engn, Wuhan 430074, Peoples R China
[4] Zhongxing Commun Co Ltd, Shenzhen 518057, Peoples R China
关键词
Numerical simulation; Heat transfer enhancement; Performance improvement; Shell-and-tube heat exchanger; Trefoil-hole baffle; Baffle distance; TRANSFER ENHANCEMENT; SIDE;
D O I
10.1016/j.applthermaleng.2015.06.012
中图分类号
O414.1 [热力学];
学科分类号
摘要
The shellside turbulent heat transfer enhancement with trefoil-hole baffles was validated in our previous experimental investigation on a small size heat exchanger. In the present work, the commercial software ANSYS FLUENT is adopted to conduct the numerical study on the thermal augmentation of trefoil-hole baffles. Structural modification is made on the small size heat exchanger for better thermo-hydraulic performances, and the effects of baffle distance are investigated. Computation results demonstrate that the current numerical model, where the whole heat exchanger, including tubes, baffles and fluids on both shell and tube sides, etc., is modeled, could predict the thermo-hydraulic performances considerably well by comparing with experimental data. Moreover, it is found that with the structural modification, the pressure loss on the shellside of the small size heat exchanger decreases by similar to 21.0%, and the shellside overall thermo-hydraulic performance rises by similar to 21.9%. In addition, the convection heat transfer coefficient on the shellside is observed to decrease monotonically with the decrement of baffle number (from 7795.4 to 6431.2 W/m(2) K at shellside Re = 11,350), while the variation tendency of shellside overall thermo-hydraulic performance with baffle number is on the opposite, with the value between 558.3 and 712.1 W/(m(2) K kPa) at shellside Re = 11,350. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:220 / 228
页数:9
相关论文
共 31 条
  • [1] Three-dimensional modeling of a Helixchanger® heat exchanger using CFD
    Andrews, MJ
    Master, BI
    [J]. HEAT TRANSFER ENGINEERING, 2005, 26 (06) : 22 - 31
  • [2] [Anonymous], 2009, ANSYS Fluent 12 Theory guide
  • [3] Deng XH, 1998, HEAT TRANSFER ENG, V19, P21
  • [4] Numerical and experimental investigation of shellside characteristics for RODbaffle heat exchanger
    Dong, Q. W.
    Wang, Y. Q.
    Liu, M. S.
    [J]. APPLIED THERMAL ENGINEERING, 2008, 28 (07) : 651 - 660
  • [5] GENTRY CC, 1990, CHEM ENG PROG, V86, P48
  • [6] PWR steam generators
    Green, SJ
    Hetsroni, G
    [J]. INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 1995, 21 : 1 - 97
  • [7] Holman J.P., 1997, HEAT TRANSF
  • [8] Jiao L, 2011, THESIS HUAZHONG U SC
  • [9] Helical baffles in shell-and-tube heat exchangers .1. Experimental verification
    Kral, D
    Stehlik, P
    vanderPloeg, HJ
    Master, BI
    [J]. HEAT TRANSFER ENGINEERING, 1996, 17 (01) : 93 - 101
  • [10] Analysis of local shellside heat and mass transfer in the shell-and-tube heat exchanger with disc-and-doughnut baffles
    Li, H
    Kottke, V
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1999, 42 (18) : 3509 - 3521