Optimization of an Air-PCM heat exchanger and elaboration of peak power reduction strategies

被引:35
作者
El Mankibi, Mohamed [1 ]
Stathopoulos, Nikolaos [1 ]
Rezai, Niousha [1 ]
Zoubir, Amine [1 ]
机构
[1] Univ Lyon, Ecole Natl Travaux Publ Etat ENTPE, Bldg & Civil Engn Lab LGCB, F-69120 Vaulx En Velin, France
关键词
Latent thermal storage; Optimization; PCM heat exchanger; Peak power reduction; Load shifting; THERMAL-ENERGY STORAGE; BUILDINGS; SYSTEM;
D O I
10.1016/j.enbuild.2015.05.023
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Phase Change Materials (PCM) technology can be used for thermal storage and peak load shaving. This paper presents the optimization study of a PCM-Air heat exchanger as well as the development of load shifting solutions which take into account the thermal comfort of the occupants and the indoor air quality. The exchanger contains macroencapsumated PCM (paraffin) and is conceived in a way that facilitates its integration in a ventilation system. It is aimed to shift space heating electrical consumption from peak to off-peak period. The study is performed using an experimentally validated numerical model based on the heat balance approach and the apparent heat capacity method. Several parameters were investigated during the optimization processes, including heat exchanger dimensions, PCM quantity and properties, seeking the configuration with the optimal compromise between stored heat and the time needed for the charging/discharging process. The numerical model was coupled to a building simulation model with several control strategies investigating different scenarios over a one- month winter period. The scenarios vary with increasing complexity, first considering load shifting and thermal comfort, then adding the final price of electricity consumption and finally taking into account the indoor air quality. (C) 2015 Elsevier B.V. All rights reserved.
引用
收藏
页码:74 / 86
页数:13
相关论文
共 50 条
[21]   Optimization of the heat exchanger of an air conditioning system [J].
Chichindaev, A ;
Dyachenko, Y .
KORUS 2003: 7TH KOREA-RUSSIA INTERNATIONAL SYMPOSIUM ON SCIENCE AND TECHNOLOGY, VOL 1 PROCEEDINGS: MACHINE PARTS AND MATERIALS PROCESSING, 2003, :255-259
[22]   Inverse method to estimate air flow rate during free cooling using PCM-air heat exchanger [J].
Ousegui, A. ;
Marcos, B. ;
Havet, M. .
APPLIED THERMAL ENGINEERING, 2019, 146 :432-439
[23]   Numerical study of a PCM-air heat exchanger's thermal performance [J].
Herbinger, F. ;
Bhouri, M. ;
Groulxl, D. .
7TH EUROPEAN THERMAL-SCIENCES CONFERENCE (EUROTHERM2016), 2016, 745
[24]   Experimental validation of an air-PCM storage unit comparing the effective heat capacity and enthalpy methods through CFD simulations [J].
Iten, Muriel ;
Liu, Shuli ;
Shukla, Ashish .
ENERGY, 2018, 155 :495-503
[25]   Design optimization of finned multi-tube PCM heat exchanger for enhancing EV energy performance [J].
Kim, Hyuntae ;
Oh, Jinwoo ;
Hong, Jangpyo ;
Choi, Hongseok ;
Kim, Hayeon ;
Lee, Hoseong .
APPLIED THERMAL ENGINEERING, 2024, 257
[26]   Experimental and numerical investigation of a real-scale air to multiple PCM heat exchanger [J].
Kareem, Bashir Eskander ;
Adham, Ahmed Mohammed ;
Yaqob, Banipal Nanno .
JOURNAL OF BUILDING ENGINEERING, 2024, 89
[27]   Enhancement of an air conditioning system performance utilizing a PCM-based heat exchanger: Impact of aspect ratio [J].
Singh, Prakash Chandra ;
Halder, Pabitra .
NUMERICAL HEAT TRANSFER PART A-APPLICATIONS, 2024,
[28]   Characterization of melting and solidification in a real scale PCM-air heat exchanger: Numerical model and experimental validation [J].
Dolado, Pablo ;
Lazaro, Ana ;
Marin, Jose M. ;
Zalba, Belen .
ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (04) :1890-1907
[29]   Parametric Optimization of Earth to Air Heat Exchanger Using Response Surface Method [J].
Maoz ;
Ali, Saddam ;
Muhammad, Noor ;
Amin, Ahmad ;
Sohaib, Mohammad ;
Basit, Abdul ;
Ahmad, Tanvir .
SUSTAINABILITY, 2019, 11 (11)
[30]   A new ventilated window with PCM heat exchanger-Performance analysis and design optimization [J].
Hu, Yue ;
Heiselberg, Per Kvols .
ENERGY AND BUILDINGS, 2018, 169 :185-194