Optimal location and sizing determination of Distributed Generation and DSTATCOM using Particle Swarm Optimization algorithm

被引:175
作者
Devi, S. [1 ]
Geethanjali, M. [2 ]
机构
[1] Natl Coll Engn, Dept EEE, Tirunelveli 627151, India
[2] Thiagarajar Coll Engn, Dept EEE, Madurai 625015, Tamil Nadu, India
关键词
Distributed Generation (DG); Distribution Static Compensator (DSTATCOM); Radial Distribution System (RDS); Loss Sensitivity Factor (LSF); Particle Swarm Optimization (PSO); DISTRIBUTION-SYSTEMS; POWER-FLOW; CAPACITOR ALLOCATION; PLACEMENT;
D O I
10.1016/j.ijepes.2014.05.015
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A Particle Swarm Optimization algorithm for finding the optimal location and sizing of Distributed Generation and Distribution STATicCOMpensator (DSTATCOM) with the aim of reducing the total power loss along with voltage profile improvement of Radial Distribution System is proposed in this paper. The new-fangled formulation projected is inspired by the idea that the optimum placement of the DG and DSTATCOM can facilitate in minimization of the line loss and voltage dips in Radial Distribution Systems. A complete performance analysis is carried out on 12, 34 and 69 bus radial distribution test systems and each test system has five different cases. The results analyzed using Loss Sensitivity Factor shows the optimal placement and sizing of DG and DSTATCOM in Radial Distribution System effectively improves the voltage profile and reduces the total power losses of the system. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:562 / 570
页数:9
相关论文
共 26 条
[2]   Distributed generation:: a definition [J].
Ackermann, T ;
Andersson, G ;
Söder, L .
ELECTRIC POWER SYSTEMS RESEARCH, 2001, 57 (03) :195-204
[3]  
[Anonymous], 1976, IEEE PES WINTER M
[4]  
[Anonymous], J ELECT SYST
[5]   Optimal allocation of capacitors in unbalanced multi-converter distribution systems: A comparison of some fast techniques based on genetic algorithms [J].
Carpinelli, G. ;
Proto, D. ;
Noce, C. ;
Russo, A. ;
Varilone, P. .
ELECTRIC POWER SYSTEMS RESEARCH, 2010, 80 (06) :642-650
[6]   An improved backward/forward sweep load flow algorithm for radial distribution systems [J].
Chang, G. W. ;
Chu, S. Y. ;
Wang, H. L. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (02) :882-884
[7]   A minimal harmonic controller for a STATCOM [J].
Chen, Ben-Sheng ;
Hsu, Yuan-Yih .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2008, 55 (02) :655-664
[8]   Application of Modified Bacterial Foraging Optimization algorithm for optimal placement and sizing of Distributed Generation [J].
Devi, S. ;
Geethanjali, M. .
EXPERT SYSTEMS WITH APPLICATIONS, 2014, 41 (06) :2772-2781
[9]   Optimal Capacitor Placement and Sizing in Unbalanced Distribution Systems With Harmonics Consideration Using Particle Swarm Optimization [J].
Eajal, Abdelsalam A. ;
El-Hawary, M. E. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (03) :1734-1741
[10]  
Eberhart RC, 2001, IEEE C EVOL COMPUTAT, P81, DOI 10.1109/CEC.2001.934374