Experimental investigation on compressed air drying performance using pressurized liquid desiccant

被引:6
作者
Yin, Yonggao [1 ,2 ,3 ]
Zheng, Baojun [1 ]
Shao, Bin [1 ]
Zhang, Xiaosong [1 ,2 ,3 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Jiangsu, Peoples R China
[2] Southeast Univ, Minist Educ, Key Lab Energy Thermal Convers & Control, Nanjing 210096, Jiangsu, Peoples R China
[3] Southeast Univ, Jiangsu Prov Key Lab Solar Energy Sci & Technol, Nanjing 210096, Jiangsu, Peoples R China
关键词
Compressed air; drying performance; energy analysis; experiment; liquid desiccant; pressurized dehumidifier; RESEARCH-AND-DEVELOPMENT; DEHUMIDIFIER; TEMPERATURE; SYSTEMS; BED;
D O I
10.1080/07373937.2015.1057838
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
As a new compressed air-drying method, the compressed air dehumidification using a pressurized liquid desiccant was proposed in our previous study. The pressurized dehumidifier is a complex and core component of the drying system. The mass transfer performance between the compressed air and LiCl aqueous solution is experimentally studied in a counter-flow pressurized dehumidifier filled with structured packing. The humidity ratio of outlet compressed air, vapor removal of processed compressed air, moisture removal rate, and dehumidification efficiency were selected as the performance indices. The results show that the minimum humidity ratio of processed compressed air could reach 0.23g/kg under 0.71MPa. Compressed air-drying performance could be remarkably enhanced through increasing the air pressure and liquid desiccant inlet concentration while the influence of liquid desiccant temperature is negative. Furthermore, in order to ensure high compressed air-drying performance, reduce the power consumption of the air compressor and liquid desiccant pump, and the possibility of carryover, the optimum ratio of liquid to compressed air flow rate is recommended to be around 1.5 under pressure around 0.50MPa. Meanwhile, the energy consumption for per-gram moisture removal of a liquid-desiccant-based compressed air-drying system can reach 1.42kJ/g lower than cooling dehumidification under 0.3MPa, which is 16.0% lower than a compressed air-cooling dehumidification system.
引用
收藏
页码:372 / 382
页数:11
相关论文
共 31 条
[1]   Effect of structured packing density on performance of air dehumidifier [J].
Abdul-Wahab, SA ;
Abu-Arabi, MK ;
Zurigat, YH .
ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (15-16) :2539-2552
[2]   Low grade thermal energy sources and uses from the process industry in the UK [J].
Ammar, Yasmine ;
Joyce, Sharon ;
Norman, Rosemary ;
Wang, Yaodong ;
Roskilly, Anthony P. .
APPLIED ENERGY, 2012, 89 (01) :3-20
[3]  
[Anonymous], 1327712008 GBT
[4]   Optimized solar-powered liquid desiccant system to supply building fresh water and cooling needs [J].
Audah, N. ;
Ghaddar, N. ;
Ghali, K. .
APPLIED ENERGY, 2011, 88 (11) :3726-3736
[5]   A novel method to evaluate the performance of liquid desiccant air dehumidifier system [J].
Bakhtiar, Agung ;
Rokhman, Fatkhur ;
Choi, Kwang Hwan .
ENERGY AND BUILDINGS, 2012, 44 :39-44
[6]   An experimental study of structured packing dehumidifier/regenerator operating with liquid desiccant [J].
Bassuoni, M. M. .
ENERGY, 2011, 36 (05) :2628-2638
[7]   Heat pump drying: Recent developments and future trends [J].
Chua, KJ ;
Chou, SK ;
Ho, JC ;
Hawlader, MNA .
DRYING TECHNOLOGY, 2002, 20 (08) :1579-1610
[8]   Properties of aqueous solutions of lithium and calcium chlorides: formulations for use in air conditioning equipment design [J].
Conde, MR .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2004, 43 (04) :367-382
[9]  
Djaeni M., 2007, Drying Technology, V25, P1063
[10]   Low temperature peanut drying using liquid desiccant system climatic conditions [J].
Ertas, A ;
Azizul, HAKM ;
Kiris, I ;
Gandhidasan, P .
DRYING TECHNOLOGY, 1997, 15 (3-4) :1045-1060