Modelling of three-phase electric arc furnace for estimation of voltage flicker in power transmission network

被引:31
作者
Teklic, Ana Tomasovic [1 ]
Filipovic-Grcic, Bozidar [2 ]
Pavic, Ivica [2 ]
机构
[1] Koncar Elect Engn Inst, Zagreb 10000, Croatia
[2] Univ Zagreb, Fac Elect Engn & Comp, Zagreb 10000, Croatia
关键词
Electric arc furnace; Voltage flicker; Matlab/Simulink; Power quality; Flickermeter; MARKOV MODEL;
D O I
10.1016/j.epsr.2017.01.037
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a dynamic model of an electric arc furnace (EAF) developed in Matlab/Simulink environment. Model is based on simulating varying resistance of the electric arc in time-domain while taking into account its stochastic behaviour. The model was applied for estimation of voltage flicker in power transmission network at the point of common coupling caused by operation of EAF. Modelling and simulation of an International Eletrotechnical Commission (IEC) flickermeter were also performed in order to calculate voltage flicker from the simulated EAF voltage. In order to verify the developed EAF model, calculations of voltage flicker were compared to measurements obtained from various operating conditions of the EAF such as boring, melting and refining. Influence of short circuit power and switching operating condition of the transmission network on flicker levels at point of common coupling was investigated. (C) 2017 Elsevier B.V. All rights reserved.
引用
收藏
页码:218 / 227
页数:10
相关论文
共 28 条
[1]   Parameter Identification of Arc Furnace Based on Stochastic Nature of Arc Length Using Two-Step Optimization Technique [J].
Agah, S. M. Mousavi ;
Hosseinian, S. H. ;
Abyaneh, H. Askarian ;
Moaddabi, N. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (04) :2859-2867
[2]   An improved time domain arc furnace model for harmonic analysis [J].
Alonso, MAP ;
Donsión, MP .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :367-373
[3]  
[Anonymous], P IEEE POW EN SOC GE
[4]  
[Anonymous], TRANSIENTS TECH NOTE
[5]  
[Anonymous], INT C POW SYST TRANS
[6]  
[Anonymous], INT C REC ADV EL EL
[7]  
[Anonymous], 6100037 IEC TR
[8]  
[Anonymous], IEEE T POWER DELIVER
[9]  
[Anonymous], POW ENG SOC SUMM M I
[10]  
[Anonymous], 2010, EN Standard 50160