Experimental study on the effect of pool fire area and violent fuel boiling on fuel burning state evolution in compartment fire

被引:10
作者
Wang, Dong [1 ]
Zhou, Xiaodong [1 ]
Gui, Jia [1 ]
Ju, Xiaoyu [2 ]
Ye, Kai [3 ]
Zhou, Zhizuan [1 ]
Cao, Junda [1 ]
Zheng, Yuan [1 ]
Cao, Bei [1 ]
Yang, Lizhong [1 ]
Peng, Fei [1 ,4 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230026, Anhui, Peoples R China
[2] Toyohashi Univ Technol, Dept Mech Engn, Tempaku Ku, 1-1 Hibarigaoka, Toyohashi, Aichi 4418580, Japan
[3] Nanyang Technol Univ, Sch Mat Sci & Engn, Singapore 639798, Singapore
[4] Changsha Univ Sci & Technol, Coll Energy & Power Engn, Changsha 410114, Hunan, Peoples R China
关键词
Ventilation-controlled compartment fire; Opening factor; Burning rate; Indoor temperature; Facade flame; Violent boiling; THIN-LAYER BOILOVER; BEHAVIOR; HEIGHTS;
D O I
10.1016/j.fuel.2020.118933
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Experiments were conducted to elucidate the impact of pool area and violent liquid fuel boiling on a compartment fire evolution and facade flame. The experiments were performed in a 1/2 reduced-scale compartment, with several different-sized openings and pools. The temperatures at the inner and outer corners of the compartment, the fuel mass loss rate and the height of the facade flame ejected from the opening were analyzed. As the ratio of pool area to opening factor gradually increased, both the temperature variations at the inner and outer corners underwent three stages after the fuel boiled violently. The slope of the mass flow rate of air inflow with the burning rate gradually decreased to 8.43 as the fuel area increased. It was found that fuel pyrolysis rate was determined by opening factor and fuel area in a ventilation-controlled fire. Data from other researcher was used to verify that this inference was also applicable to different fuels. A new characteristic length was proposed to explain the evolution of facade flame height when there was a temperature difference in the enclosure.
引用
收藏
页数:11
相关论文
共 45 条
[1]  
Babrauskas V., 1980, FIRE TECHNOL, V16, P94, DOI [10.1007/BF02351801, DOI 10.1007/BF02351801]
[2]   A two-thermocouples probe for radiation corrections of measured temperatures in compartment fires [J].
Brohez, S ;
Delvosalle, C ;
Marlair, G .
FIRE SAFETY JOURNAL, 2004, 39 (05) :399-411
[3]  
Bullen ML., 1979, S INT COMBUSTION, V17, P1139, DOI [10.1016/S0082-0784(79)80108-3, DOI 10.1016/S0082-0784(79)80108-3]
[4]   Oxygen concentration effects on the burning behavior of small scale pool fires [J].
Chen, Jian ;
Zhang, Xuelin ;
Zhao, Yanli ;
Bi, Yubo ;
Li, Changhai ;
Lu, Shouxiang .
FUEL, 2019, 247 :378-385
[5]   Mass pyrolysis rates and excess pyrolysate in fully developed enclosure fires [J].
Delichatsios, MA ;
Silcock, GWH ;
Liu, XJ ;
Delichatsios, M ;
Lee, YP .
FIRE SAFETY JOURNAL, 2004, 39 (01) :1-21
[6]  
Delichatsios MA, 2003, FIRE SAFETY SCI, P59, DOI DOI 10.3801/IAFSS.FSS.7-59
[7]   The effect of azeotropic blended fuel on combustion characteristics in a ceiling vented compartment [J].
Ding, Yanming ;
Lin, Frank ;
Lu, Shouxiang ;
He, Qize ;
Wang, Changjian ;
Zhou, Ru .
FUEL, 2017, 189 :1-7
[8]   Experimental study of thin-layer boilover in large-scale pool fires [J].
Ferrero, Fabio ;
Munoz, Miguel ;
Kozanoglu, Bulent ;
Casal, Joaquim ;
Arnaldos, Josep .
JOURNAL OF HAZARDOUS MATERIALS, 2006, 137 (03) :1293-1302
[9]   Thin-layer boilover: Prediction of its onset and intensity [J].
Garo, JP ;
Vantelon, JP ;
Koseki, H .
COMBUSTION SCIENCE AND TECHNOLOGY, 2006, 178 (07) :1217-1235
[10]   A numerical study of thermal degradation of polymers: Surface and in-depth absorption [J].
Gong, Junhui ;
Chen, Yixuan ;
Jiang, Juncheng ;
Yang, Lizhong ;
Li, Jing .
APPLIED THERMAL ENGINEERING, 2016, 106 :1366-1379