Fault Location for Interline Fault of Parallel Transmission Lines Using One-terminal Data

被引:0
|
作者
Xu, Gang [1 ]
Yu, Sheng [1 ]
Xu, Zhenyu [2 ]
机构
[1] North China Elect Power Univ, Dept Elect Engn, Beijing, Peoples R China
[2] Sifang Protect Automatizat Corp, Beijing, Peoples R China
关键词
Fault currents; fault location; interline fault; load currents; parallel transmission lines; power system faults; six-component algorithm; source impedance; transition resistance; zero-sequence mutual;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
To solve the problem of Interline fault of parallel transmission lines, by means of considering the influence of zero sequence mutual inductance of parallel transmission lines a fault location algorithm based on one-terminal electrical data is proposed. Based on the analysis of the relationship of two parallel transmission lines' fault components, the fault location equation for interline fault without ground is derived by the boundary condition of interline fault mode. It is shown that the new method is independent of fault resistance, load condition and source impedance. Extensive simulation studies using PSCAD/EMTDC have verified that this approach can obtain a highly accurate fault distance, it is also proved that the proposed algorithm is independent of transition resistance, system impedance and load situation.
引用
收藏
页码:2014 / +
页数:2
相关论文
共 50 条
  • [21] Study on impedance-traveling wave assembled algorithm in one-terminal fault location system for transmission lines
    Zheng, Xiuyu
    Li, Xiaoming
    Ding, Jianyong
    Duan, Zhiyuan
    2008 THIRD INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES, VOLS 1-6, 2008, : 1723 - 1726
  • [22] Electrical Power Systems Fault Location with One-Terminal Data Using Estimated Remote Source Impedance
    Lima, D. A. C.
    Ferraz, R. G.
    Filomena, A. D.
    Bretas, A. S.
    2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,
  • [23] Fault Location of Aircraft Cable Based on One-Terminal Electrical Quantities
    Liu, Xiaolin
    Zhang, Zhenzhen
    Jing, Tao
    Shi, Xudong
    PROCEEDINGS OF THE 2011 INTERNATIONAL CONFERENCE ON INFORMATICS, CYBERNETICS, AND COMPUTER ENGINEERING (ICCE2011), VOL 1: INTELLIGENT CONTROL AND NETWORK COMMUNICATION, 2011, 110 (01): : 9 - 15
  • [24] A fault location method for parallel transmission lines
    Sheng, LB
    Elangovan, S
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1999, 21 (04) : 253 - 259
  • [25] Fault Location of Aircraft Cable Based on One-terminal Electrical Quantities
    Liu, Xiaolin
    Zhang, Zhenzhen
    Jing, Tao
    Shi, Xudong
    2010 INTERNATIONAL COLLOQUIUM ON COMPUTING, COMMUNICATION, CONTROL, AND MANAGEMENT (CCCM2010), VOL I, 2010, : 186 - 189
  • [26] Study of fault location for parallel transmissions lines using one terminal current traveling waves
    Bian Haihong
    Xu Qingshan
    2008 THIRD INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES, VOLS 1-6, 2008, : 2296 - 2301
  • [27] Robustness of one-terminal fault location algorithm based on power frequency quantities
    Chen, Z
    Dong, XZ
    Lou, CM
    2002 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, VOLS 1-3, CONFERENCE PROCEEDINGS, 2002, : 1118 - 1122
  • [28] DEVELOPMENT OF A NEW TYPE FAULT LOCATOR USING THE ONE-TERMINAL VOLTAGE AND CURRENT DATA
    TAKAGI, T
    YAMAKOSHI, Y
    YAMAURA, M
    KONDOW, R
    MATSUSHIMA, T
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (08): : 2892 - 2898
  • [29] Fault location for two- and three-terminal parallel lines using synchronized data
    Stamp, Jason
    Girgis, Adly A.
    International Journal of Power and Energy Systems, 1999, 19 (03): : 212 - 217
  • [30] Two-terminal fault location algorithm uninfluenced by parameters of parallel transmission lines
    Xi'an Jiaotong University, Xi'an 710049, China
    Dianli Xitong Zidonghue, 2006, 24 (21-26+32):