Power frequency secondary arc current in uncompensated EHV AC mixed cable-overhead lines

被引:6
|
作者
Gatta, F. M. [1 ]
Geri, A. [1 ]
Lauria, S. [1 ]
Maccioni, M. [1 ]
机构
[1] Univ Roma La Sapienza, Dept Astronaut Elect & Energet Engn, I-00184 Rome, Italy
关键词
HV ac transmission lines; Underground cables; Mixed lines; Secondary arc current; Single-pole autoreclosure; STATE OPERATING-CONDITIONS; SYSTEMS; SIMULATION;
D O I
10.1016/j.epsr.2014.01.020
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper deals with the secondary arc current and recovery voltage in Extra-High Voltage (EHV) ac mixed lines (MLs), i.e. solidly series-connected overhead line (OHL) and underground cable (CL) sections, during the dead time of single-pole auto-reclosure (SPAR) cycles, following single-phase-to-ground faults in the overhead line sections. Secondary arc current and recovery voltage are investigated at first by an analytical approach, assessing power-frequency quantities on a simplified equivalent circuit model of MLs. A parametric analysis of uncompensated 400 kV-50 Hz mixed lines and the comparison with overhead lines of equal length have been subsequently carried out by a multiconductor simulation program. Results show that the inclusion of short underground cable stretches in mixed lines has two main effects: an increase of secondary arc current and a concurrent reduction of the recovery voltage in comparison to overhead lines. The study evidences possible criticalities during SPAR in some typical 400 kV-50 Hz mixed line configurations and operating conditions: secondary arc currents may be 50% higher than in 400 kV OHLs of equal length and can be greater than 50 divided by 60A. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:14 / 21
页数:8
相关论文
共 28 条
  • [1] Single-Pole Autoreclosure in uncompensated EHV AC mixed overhead-cable lines: A parametric time-domain analysis
    Gatta, F. M.
    Geri, A.
    Graziani, M.
    Lauria, S.
    Maccioni, M.
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 210
  • [2] Characteristics of PLC Channels over High Voltage Power Cables and Mixed Cable-Overhead High Voltage Power Lines
    Kharlamov, Vasiliy V.
    Romanov, Sergey E.
    Shkarin, Yuri P.
    Merkulov, Anton G.
    2019 IEEE 1ST GLOBAL POWER, ENERGY AND COMMUNICATION CONFERENCE (GPECOM2019), 2019, : 35 - 40
  • [3] Shunt compensation of EHV cables and mixed overhead-cable lines
    Lauria, Stefano
    Gatta, Fabio M.
    Colla, Luigi
    2007 IEEE LAUSANNE POWERTECH, VOLS 1-5, 2007, : 1344 - +
  • [4] Operating capability of ac EHV mixed lines with overhead and cables links
    Benato, Roberto
    Paolucci, Antonio
    ELECTRIC POWER SYSTEMS RESEARCH, 2008, 78 (04) : 584 - 594
  • [5] HV and EHV power cable lines AC-service experiences
    Rakowska, Aleksandra
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (06): : 85 - 88
  • [6] Characteristics of Secondary Arc Current on UHV DC and EHV AC Transmission Lines Erected on the Same Tower
    Xie, Yadi
    He, Baina
    Wang, Lemiao
    Jiang, Renzhuo
    Zhou, Yuyang
    Mao, Yazhe
    INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2019, 20 (05)
  • [7] Effects of grounding resistance on secondary arc current in EHV Transmission lines
    Han, YH
    Li, H
    Deng, QQ
    Shi, W
    POWERCON 2002: INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS 1-4, PROCEEDINGS, 2002, : 784 - 787
  • [8] Study of power frequency arc of composite insulators for overhead lines
    Wu, Guangya
    Lin, Xiuqin
    Cai, Wei
    Zhang, Rui
    Xiao, Guoying
    Gu, Guanghe
    Gaodianya Jishu/High Voltage Engineering, 2002, 28 (11):
  • [9] Factors affecting secondary arc current in EHV lines with single pole auto reclosing
    Sastry, V.R.
    Dunn, C.J.
    Journal of Electrical and Electronics Engineering, Australia, 1988, 8 (02): : 140 - 144
  • [10] AC potential on pipelines nearby EHV power lines due to Low Frequency Induction
    Al Shahri, Ahmed S.
    Nair, Nirmal-Kumar C.
    2015 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING CONFERENCE (AUPEC), 2015,