Comparison between IEEE and CIGRE Thermal Behaviour Standards and Measured Temperature on a 132-kV Overhead Power Line

被引:54
|
作者
Arroyo, Alberto [1 ]
Castro, Pablo [1 ]
Martinez, Raquel [1 ]
Manana, Mario [1 ]
Madrazo, Alfredo [1 ]
Lecuna, Ramon [1 ]
Gonzalez, Antonio [2 ]
机构
[1] Univ Cantabria, Elect & Energy Dept, E-39005 Santander, Spain
[2] Viesgo, Santander 39011, Spain
来源
ENERGIES | 2015年 / 8卷 / 12期
关键词
thermal rating; ampacity; overhead line temperature; weather parameters; real-time monitoring; TRANSMISSION; AMPACITY; SYSTEM;
D O I
10.3390/en81212391
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents the steady and dynamic thermal balances of an overhead power line proposed by CIGRE (Technical Brochure 601, 2014) and IEEE (Std.738, 2012) standards. The estimated temperatures calculated by the standards are compared with the averaged conductor temperature obtained every 8 min during a year. The conductor is a LA 280 Hawk type, used in a 132-kV overhead line. The steady and dynamic state comparison shows that the number of cases with deviations to conductor temperatures higher than 5 degrees C decreases from around 20% to 15% when the dynamic analysis is used. As some of the most critical variables are magnitude and direction of the wind speed, ambient temperature and solar radiation, their influence on the conductor temperature is studied. Both standards give similar results with slight differences due to the different way to calculate the solar radiation and convection. Considering the wind, both standards provide better results for the estimated conductor temperature as the wind speed increases and the angle with the line is closer to 90 degrees In addition, if the theoretical radiation is replaced by that measured with the pyranometer, the number of samples with deviations higher than 5 degrees C is reduced from around 15% to 5%.
引用
收藏
页码:13660 / 13671
页数:12
相关论文
empty
未找到相关数据