Classroom Carbon Dioxide Concentration, School Attendance, and Educational Attainment

被引:78
作者
Gaihre, Santosh [1 ]
Semple, Sean [1 ]
Miller, Janice [1 ]
Fielding, Shona [2 ]
Turner, Steve [1 ]
机构
[1] Royal Aberdeen Childrens Hosp, Aberdeen AB25 2ZG, Scotland
[2] Dept Med Stat, Aberdeen AB25 2ZD, Scotland
关键词
academic performance; carbon dioxide; indoor air quality; schools; school absence; temperature; INDOOR AIR-QUALITY; PARTICULATE MATTER; CO2; CONCENTRATIONS; VENTILATION RATES; HEALTH; CHILDREN; ASTHMA; ASSOCIATION; PERFORMANCE; RESPONSES;
D O I
10.1111/josh.12183
中图分类号
G40 [教育学];
学科分类号
040101 ; 120403 ;
摘要
BACKGROUND: We tested the hypothesis that classroom carbon dioxide (CO2) concentration is inversely related to child school attendance and educational attainment. METHODS: Concentrations of CO2 were measured over a 3-5 day period in 60 naturally ventilated classrooms of primary school children in Scotland. Concentrations of CO2 were related to the class average annual attendance and proportions attaining a national standard for reading, writing, and numeracy, adjusted for socioeconomic status and class size. RESULTS: The median (interquartile range, IQR) CO2 concentration averaged over the school day was 1086 ppm (922, 1310). In the model, Time Weighted Average CO2 concentrations were inversely associated with school attendance but not academic attainments. An increase of 100 ppm CO2 was associated with a reduced annual attendance of 0.2% (0.04, 0.4) roughly equivalent to 1 half day of school per annum, assuming schools are open on 190 days per year. Indoor temperature and relative humidity were not related to attendance or academic attainment. CONCLUSIONS: Inadequate classroom ventilation, as evidenced by CO2 concentration exceeding 1000 ppm, is not uncommon and may be associated with reduced school attendance. A relationship between inadequate classroom ventilation and adverse health outcomes in children may be present and this needs to be explored.
引用
收藏
页码:569 / 574
页数:6
相关论文
共 30 条
[1]  
AK - PERSILY., 1997, ASHRAE Transactions, V103, pt. 2, P4072
[2]  
American Society of Heating Refrigerating and Air Conditioning Engineers. Standard 62, 1989, 62 AM SOC HEAT REFR
[3]   Poor air quality in classrooms related to asthma and rhinitis in primary schoolchildren of the French 6 Cities Study [J].
Annesi-Maesano, Isabella ;
Hulin, Marion ;
Lavaud, Francois ;
Raherison, Chantal ;
Kopferschmitt, Christine ;
de Blay, Frederic ;
Charpin, Denis Andre ;
Denis, Caillaud .
THORAX, 2012, 67 (08) :682-688
[4]  
[Anonymous], 2006, BUILD B VENT SCH BUI, V101, P101
[5]  
[Anonymous], 1996, INDOOR AIR
[6]   Ventilation rates in schools and pupils' performance [J].
Bako-Biro, Zs. ;
Clements-Croome, D. J. ;
Kochhar, N. ;
Awbi, H. B. ;
Williams, M. J. .
BUILDING AND ENVIRONMENT, 2012, 48 :215-223
[7]   Indoor air quality, ventilation and health symptoms in schools: an analysis of existing information [J].
Daisey, JM ;
Angell, WJ ;
Apte, MG .
INDOOR AIR, 2003, 13 (01) :53-64
[8]   Indoor air quality and respiratory health of children [J].
Franklin, Peter J. .
PAEDIATRIC RESPIRATORY REVIEWS, 2007, 8 (04) :281-286
[9]   Comparing the effectiveness of interventions to improve ventilation behavior in primary schools [J].
Geelen, L. M. J. ;
Huijbregts, M. A. J. ;
Ragas, A. M. J. ;
Bretveld, R. W. ;
Jans, H. W. A. ;
van Doorn, W. J. ;
Evertz, S. J. C. J. ;
van der Zijden, A. .
INDOOR AIR, 2008, 18 (05) :416-424
[10]   Control of CO2 in a naturally ventilated classroom [J].
Griffiths, M. ;
Eftekhari, M. .
ENERGY AND BUILDINGS, 2008, 40 (04) :556-560