Design Consideration of a Dual-Functional Bridge-Type Fault Current Limiter

被引:15
作者
Jiang, Fei [1 ]
Cheng, Siju [1 ]
Tu, Chunming [2 ]
Guo, Qi [2 ]
Zhu, Rongwu [3 ]
Li, Xiaoyun [4 ]
Liserre, Marco [3 ]
机构
[1] Changsha Univ Sci & Technol, Sch Elect & Informat Engn, Changsha 410004, Peoples R China
[2] Hunan Univ, Coll Elect & Informat Engn, Changsha 410082, Hunan, Peoples R China
[3] Univ Kiel, Chair Power Elect, D-24143 Kiel, Germany
[4] Nanping Power Supply Co State Grid, Nanping 353006, Peoples R China
基金
中国国家自然科学基金;
关键词
Circuit faults; Fault currents; Fault current limiters; Topology; Rectifiers; Inductors; Insulated gate bipolar transistors; Bridge-type fault current limiter (BTFCL); dual functional; dynamic voltage restorer (DVR); switching; FCL; INTERRUPTION; ENHANCEMENT; PERFORMANCE;
D O I
10.1109/JESTPE.2019.2944743
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
To sufficiently utilize a bridge-type fault current limiter (BTFCL) in the distribution grids, this article proposes a dual-functional BTFCL (DF-BTFCL), which can work either at the BTFCL mode to limit faulty currents or at the dynamic voltage restorer (DVR) mode to compensate grid-voltage fluctuations. The proposed DF-BTFCL can flexibly switch between the two modes by either activating a dc capacitive circuit or a dc inductive circuit. The inductive circuit can adjust the equivalent series impedance to limit the faulty current in an acceptable range, and the dc capacitance circuit can provide dc support to enable the DVR operation. The proposed DF-BTFCL can immediately limit the increasing rate of the faulty current without any fault detection delay, and it is similar to the conventional BTFCL. Transient processes between the switch of the two operation modes are analyzed, and the key parameters of the DF-BTFCL system are designed in detail. Simulations and experimental results both clearly prove the feasibility and effectiveness of the proposed DF-BTFCL.
引用
收藏
页码:3825 / 3834
页数:10
相关论文
共 42 条
  • [1] Survey of Solid-State Fault Current Limiters
    Abramovitz, Alexander
    Smedley, Keuye Ma
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2012, 27 (06) : 2770 - 2782
  • [2] Fault Current Interruption by the Dynamic Voltage Restorer
    Ajaei, Firouz Badrkhani
    Farhangi, Shahrokh
    Iravani, Reza
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (02) : 903 - 910
  • [3] [Anonymous], 2007, IEEE Latin America Transactions, DOI DOI 10.1109/TLA.2007.4378523
  • [4] Comparison of high-power IGBT's and hard-driven GTO's for high-power inverters
    Bernet, S
    Teichmann, R
    Zuckerberger, A
    Steimer, PK
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1999, 35 (02) : 487 - 495
  • [5] FAULT CURRENT LIMITER USING A SUPERCONDUCTING COIL
    BOENIG, HJ
    PAICE, DA
    [J]. IEEE TRANSACTIONS ON MAGNETICS, 1983, 19 (03) : 1051 - 1053
  • [6] Chen G, 2004, 2004 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1 AND 2, P1468
  • [7] Analysis of a Switched Impedance Transformer-Type Nonsuperconducting Fault Current Limiter
    Chen, Song
    Li, Peng
    Ball, Roy
    de Palma, Jean-Francois
    Lehman, Brad
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2015, 30 (04) : 1925 - 1936
  • [8] A series compensator with fault current limiting function
    Choi, SS
    Wang, TX
    Vilathgamuwa, DM
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (03) : 2248 - 2256
  • [9] Novel bridge-type FCL based on self-turnoff devices for three-phase power systems
    Fei, WanMin
    Zhang, YanLi
    Lue, ZhengYu
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) : 2068 - 2078
  • [10] Improving Fault Ride-Through Capability of Fixed-Speed Wind Turbine by Using Bridge-Type Fault Current Limiter
    Firouzi, M.
    Gharehpetian, G. B.
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2013, 28 (02) : 361 - 369