Analysis of PD-generated SF6 decomposition gases adsorbed on carbon nanotubes

被引:64
作者
Ding, Weidong
Hayashi, Ryota
Ochi, Kohei
Suehiro, Junya
Imasaka, Kiminobu
Hara, Masanori
Sano, Noriaki
Nagao, Eiichi
Minagawa, Tadao
机构
[1] Kyushu Univ, Grad Sch Informat Sci & Elect Engn, Higashi Ku, Fukuoka 8128581, Japan
[2] Univ Hyogo, Himeji Inst Technol, Himeji, Hyogo 6712201, Japan
[3] Mitsubishi Electr Corp, Transmiss & Distribut Syst Ctr, Amagasaki, Hyogo 6618661, Japan
关键词
partial discharge (PD); SF6; decomposition gas; carbon nanotube; Fourier transformation infrared spectroscopy (FTIR); molecular orbital calculation;
D O I
10.1109/TDEI.2006.258191
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Chemical byproducts analysis has been recognized as a powerful diagnosis method for SF6 gas-insulated switchgear (GIS). The authors have previously demonstrated that a carbon nanotube (CNT) gas sensor could detect partial discharge (PD) generated in SF6 gas. However, PD-generated decomposition gas species, which were responsible for the CNT gas sensor response, have not been identified yet. In this paper, two kinds of experiments were conducted in order to identify the responsible decomposition gas species. At first, the decomposition gas molecules adsorbed on CNTs were analyzed by Fourier transformation infrared (FTIR) spectroscopy. FTIR absorbance was observed around 735 cm(-1) after CNTs were exposed to PD generated in SF6. In the second experiment, the CNT gas sensor responses to typical SF6 decomposition products (HF and SF4) were examined. The CNT gas sensor responded to these gases in the same way as to PD generated in SF6. SF4 response was larger than HF response. Based on these results, SF4 and SOF2 emerged as candidates for the responsible decomposition gases. Electrochemical interactions between adsorbed gas molecules and CNT were discussed based on theoretical predictions of molecular orbital calculations. The calculation results suggested that both of SOF2 and SF4 could increase the CNT gas sensor conductance.
引用
收藏
页码:1200 / 1207
页数:8
相关论文
共 26 条
[1]  
[Anonymous], 2003, Gaussian 03 User's Reference
[2]   Influence of reactive SFx gases on electrode surfaces after electrical discharges under SF6 atmosphere [J].
Beyer, C ;
Jenett, H ;
Klockow, D .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2000, 7 (02) :234-240
[3]   NOVEL LOW-COST SF6 ARCING BY-PRODUCT DETECTORS FOR FIELD USE IN GAS-INSULATED SWITCHGEAR [J].
BRAUN, JM ;
CHU, FY .
IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (02) :81-86
[4]   Spark decomposition of SF6, SF6/N2 (10:90 and 5:95) mixtures in the presence of solid additives (polyethylene, polypropylene or Teflon), gaseous additives (methane, ethylene, octofluoropropane, carbon monoxide or dioxide), water or oxygen [J].
Casanovas, AM ;
Diaz, J ;
Casanovas, J .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2002, 35 (20) :2558-2569
[5]   STUDY OF THE DECOMPOSITION OF WET SF6, SUBJECTED TO 50-HZ AC CORONA DISCHARGES [J].
DERDOURI, A ;
CASANOVAS, J ;
HERGLI, R ;
GROB, R ;
MATHIEU, J .
JOURNAL OF APPLIED PHYSICS, 1989, 65 (05) :1852-1857
[6]  
Ding W, 2005, 2005 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, P561
[7]  
DING W, IN PRESS IEEE T DIEL
[8]  
DING W, 2004, P 12 AS C EL DISCH S, P175
[9]   Sensitivity of ammonia interaction with single-walled carbon nanotube bundles to the presence of defect sites and functionalities [J].
Feng, X ;
Irle, S ;
Witek, H ;
Morokuma, K ;
Vidic, R ;
Borguet, E .
JOURNAL OF THE AMERICAN CHEMICAL SOCIETY, 2005, 127 (30) :10533-10538
[10]   Gas analysis by infrared spectroscopy as a tool for electrical fault diagnostics in SF6 insulated equipment [J].
Heise, HM ;
Kurte, R ;
Fischer, P ;
Klockow, D ;
Janissek, PR .
FRESENIUS JOURNAL OF ANALYTICAL CHEMISTRY, 1997, 358 (7-8) :793-799