A Hybrid Transformer PD Monitoring Method Using Simultaneous IEC60270 and RF Data

被引:11
作者
Firuzi, Keyvan [1 ]
Vakilian, Mehdi [1 ]
Phung, B. Toan [2 ]
Blackburn, Trevor R. [2 ]
机构
[1] Sharif Univ Technol, Dept Elect Engn, Tehran 14588, Iran
[2] Univ New South Wales, Sch Elect Engn & Telecommun, Sydney, NSW 2052, Australia
关键词
Power transformer; online monitoring; partial discharges; IEC60270; RF method; stream clustering; density grids and micro-PRPD; ON-FIELD MEASUREMENTS; PARTIAL-DISCHARGE; PATTERN-RECOGNITION; S TRANSFORM; SEPARATION; INFERENCE; PULSES;
D O I
10.1109/TPWRD.2019.2900322
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Transformers are the key component in power system transmission and distribution networks. Condition-based maintenance will increase their expected life, and online monitoring is essential to ensure operation reliability. In this paper, a new approach to transformer online monitoring is provided based on partial discharge (PD) measurement. Simultaneous measurements of PD using IEC60270 and radio frequency (RF) techniques are employed to explore new features that can be used to distinguish between internal PDs and external interference, as well as among different internal PD sources. Stream clustering based on the density grid method with only a few features required is used to categorize active sources without requiring large storage of information. Active source identification is performed using feature extraction from micro-phase-resolved PD images with the histogram of oriented gradient method and a pre-trained network. Two experimental case studies are conducted to evaluate the effectiveness of the proposed method, one to demonstrate the distinction between internal and external sources and the other to demonstrate the distinction between different internal PD sources. It is shown that the proposed method for online monitoring of transformers using simultaneous measurement of PD with IEC60270 and RF techniques and stream clustering is very effective in distinguishing and identifying various PD sources without the requirement of large storage of data.
引用
收藏
页码:1374 / 1382
页数:9
相关论文
共 32 条
[1]  
Aggarwal C. C., 2007, DATA STREAMS MODELS, V31, P17
[2]   On the Use of Monopole Antennas for Determining the Effect of the Enclosure of a Power Transformer Tank in Partial Discharges Electromagnetic Propagation [J].
Albarracin, Ricardo ;
Alfredo Ardila-Rey, Jorge ;
Mas'ud, Abdullahi Abubakar .
SENSORS, 2016, 16 (02)
[3]   A method for discriminating original pulses in online partial discharge measurement [J].
Allahbakhshi, Mehdi ;
Akbari, Asghar .
MEASUREMENT, 2011, 44 (01) :148-158
[4]  
[Anonymous], MEASUREMENT PARTIAL
[5]   Partial Discharge and Noise Separation by Means of Spectral-power Clustering Techniques [J].
Ardila-Rey, J. A. ;
Martinez-Tarifa, J. M. ;
Robles, G. ;
Rojas-Moreno, M. V. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (04) :1436-1443
[6]   Principal component and hierarchical cluster analyses as applied to transformer partial discharge data with particular reference to transformer condition monitoring [J].
Babnik, Tadeja ;
Aggarwal, Raj K. ;
Moore, Philip J. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) :2008-2016
[7]   Advanced PD inference in on-field measurements. Part I: Noise rejection [J].
Cavallini, A ;
Contin, A ;
Montanari, GC ;
Puletti, F .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2003, 10 (02) :216-224
[8]   Advanced PD inference in on-field measurements. Part 2: Identification of defects in solid insulation systems [J].
Cavallini, A ;
Conti, M ;
Contin, A ;
Montanari, GC .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2003, 10 (03) :528-538
[9]   Time-frequency Sparsity Map on Automatic Partial Discharge Sources Separation for Power Transformer Condition Assessment [J].
Chan, Jeffery C. ;
Ma, Hui ;
Saha, Tapan K. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (04) :2271-2283
[10]  
Christopher M. B., 2016, PATTERN RECOGN, P17