Development of a Proposed Single-Phase Series Active Power Filter without External Power Sources

被引:8
作者
Torre, Joao L. [1 ]
Barros, Luis A. M. [1 ]
Afonso, Joao L. [1 ]
Pinto, J. G. [1 ]
机构
[1] Univ Minho, Ind Elect Dept, Guimaraes, Portugal
来源
2019 2ND INTERNATIONAL CONFERENCE ON SMART ENERGY SYSTEMS AND TECHNOLOGIES (SEST 2019) | 2019年
关键词
Active Power Filters; Harmonics; Power Quality; Single-Phase Series Active Power Filter; Voltage Sags; Voltage Swells;
D O I
10.1109/sest.2019.8849010
中图分类号
TP18 [人工智能理论];
学科分类号
081104 ; 0812 ; 0835 ; 1405 ;
摘要
The quality of electric power is receiving more and more attention from part of consumers, Distribution System Operators (DSO), Transmission System Operators (TSO) and other competent entities related to the electrical power system. Once the electrical Power Quality (PQ) problems have direct implications for business productivity, causing high economic losses, it is mandatory to develop solutions that mitigate these problems. Active Power Filters (APFs) are power electronic equipment capable of compensating PQ problems that have the ability to dynamically adjust their modes of operation in response to changes in load or in the power system. Among these solutions, the Series Active Power Filter (SeAPF) is specially conceived to deal with problems related to the power system voltage amplitude and waveform. Despite the ability to compensate voltage sags, voltage swells, voltage harmonics, and voltage imbalances in three-phase systems, the SeAPF has not achieved much success neither has not been widely adopted. The lack of interest in this equipment can be largely justified by its high cost and also because of some limitations presented by the SeAPF conventional topology. In this paper is presented a novel topology, as well as the control algorithms of a single-phase SeAPF that is connected directly to the power grid without the use of coupling transformers and that does not require the use of external power sources. The topology and control algorithms of the SeAPF proposed in this paper were firstly evaluated by means of simulation results obtained with PSIM software and, once validated, a laboratory prototype was developed, being presented experimental results that support the correct operation of the proposed system.
引用
收藏
页数:6
相关论文
共 15 条
[1]  
Abidin M. N. Z., 2005, 6100032 IEC, P1
[2]  
Akagi H., INT C POW EL DRIV EN, V1
[3]   Single-phase series active power filter with transformer-coupled matrix converter [J].
Buticchi, Giampaolo ;
Barater, Davide ;
Concari, Carlo ;
Franceschini, Giovanni .
IET POWER ELECTRONICS, 2016, 9 (06) :1279-1289
[4]  
CENELEC, 2005, EUR STAND, P1
[5]  
Exposto B., 2008, POWER, P1
[6]   Single-phase universal active filter without transformer [J].
Jacobina, C. B. ;
Santos, W. R. N. ;
Oliveira, A. C. ;
da Silva, E. R. C. ;
dos Santos, E. C., Jr. .
APEC 2007: TWENTY-SECOND ANNUAL IEEE APPLIED POWER ELECTRONICS CONFERENCE AND EXPOSITION, VOLS 1 AND 2, 2007, :698-+
[7]  
Javadi A, 2012, IEEE IND ELEC, P5312, DOI 10.1109/IECON.2012.6389536
[8]  
Jiang F., 2018, REV SERIES VOLTAGE S, V4
[9]  
Karimi-Ghartemani M, 2001, PROCEEDINGS OF THE 44TH IEEE 2001 MIDWEST SYMPOSIUM ON CIRCUITS AND SYSTEMS, VOLS 1 AND 2, P421, DOI 10.1109/MWSCAS.2001.986202
[10]  
Martins J.S., 2003, 3o Congresso Luso-Mocambicano de Engenharia - CLME'2003 Engenharia e Inovacao para o Desenvolvimento, P219