Time-Domain Procedures for Lightning-Induced Voltage Calculation in Electromagnetic Transient Simulators

被引:14
作者
De Conti, Alberto [1 ]
Leal, Osis E. S. [2 ,3 ]
机构
[1] Univ Fed Minas Gerais UFMG, Dept Elect Engn, Belo Horizonte, MG, Brazil
[2] Univ Fed Minas Gerais, Grad Program Elect Engn PPGEE, Belo Horizonte, MG, Brazil
[3] UTFPR Fed Univ Technol Parana, PatoBranco, Curitiba, Parana, Brazil
关键词
Lightning-induced voltages; overhead distri-bution lines; EMT simulators; OVERHEAD LINES; INDUCED OVERVOLTAGES; NUMERICAL-SOLUTION; MODEL; PERFORMANCE;
D O I
10.1109/TPWRD.2020.2982306
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, two time-domain procedures are proposed for the calculation of lightning-induced voltages using lossy transmission line models available in electromagnetic transient simulators. In both procedures, the influence of the incident electromagnetic field is represented in the form of current sources that are connected externally at the ends of the illuminated line. One of the procedures is formulated directly in the phase-domain and is compatible with the universal line model (ULM). The second procedure is formulated in the modal domain and is compatible with the transmission line model proposed by Marti. Both procedures are validated taking as reference a first order FDTD solution of telegrapher's equations considering the presence of external electromagnetic fields. It is shown that the proposed procedures can be efficiently and accurately used for the calculation of lightning-induced voltages on overhead lines.
引用
收藏
页码:397 / 405
页数:9
相关论文
共 44 条
[1]   TRANSIENT-RESPONSE OF MULTI-CONDUCTOR TRANSMISSION-LINES EXCITED BY A NONUNIFORM ELECTROMAGNETIC-FIELD [J].
AGRAWAL, AK ;
PRICE, HJ ;
GURBAXANI, SH .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 1980, 22 (02) :119-129
[2]   An Exact Closed-Form Solution for Lightning-Induced Overvoltages Calculations [J].
Andreotti, A. ;
Assante, D. ;
Mottola, F. ;
Verolino, L. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) :1328-1343
[3]  
Andreotti A., 2015, IEEE T POWER, V28, P1213
[4]  
[Anonymous], 2005, 5 INT WORKSH BIOS IN
[5]  
[Anonymous], 2013, IEEE T ELECTROMAGN C, DOI DOI 10.1109/TEMC.2012.2205001
[6]   Calculation of lightning-induced voltages with RUSCK's method in EMTP Part I: Comparison with measurements and Agrawal's coupling model [J].
Araujo, AEA ;
Paulino, JOS ;
Silva, JP ;
Dommel, HW .
ELECTRIC POWER SYSTEMS RESEARCH, 2001, 60 (01) :49-54
[7]   Lightning-induced voltages on complex distribution systems: models, advanced software tools and experimental validation [J].
Borghetti, A ;
Gutierrez, JA ;
Nucci, CA ;
Paolone, M ;
Petrache, E ;
Rachidi, F .
JOURNAL OF ELECTROSTATICS, 2004, 60 (2-4) :163-174
[8]   TRANSIENT ANALYSIS OF LOSSLESS TRANSMISSION LINES [J].
BRANIN, FH .
PROCEEDINGS OF THE INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS, 1967, 55 (11) :2012-&
[9]   On the Stability of FDTD-Based Numerical Codes to Evaluate Lightning-Induced Overvoltages in Overhead Transmission Lines [J].
Brignone, Massimo ;
Mestriner, Daniele ;
Procopio, Renato ;
Piantini, Alexandre ;
Rachidi, Fatine .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2020, 62 (01) :108-115
[10]   Evaluation of Power System Lightning Performance, Part I: Model and Numerical Solution Using the PSCAD-EMTDC Platform [J].
Brignone, Massimo ;
Delfino, Federico ;
Procopio, Renato ;
Rossi, Mansueto ;
Rachidi, Farhad .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2017, 59 (01) :137-145