An Enhanced Strategy to Inhibit Commutation Failure in Line-Commutated Converters

被引:62
作者
Mirsaeidi, Sohrab [1 ]
Dong, Xinzhou [1 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
AC faults; commutation failure; high-voltage direct current (HVdc) transmission; line-commutated converters (LCCs); LCC HVDC SYSTEM;
D O I
10.1109/TIE.2019.2896328
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Failure of the commutation process is a serious malfunction in line-commutated high-voltage direct current (HVdc) converters, which mainly occurs due to inverter ac faults and may lead to outage of the HVdc system. In this paper, an improved strategy is developed that functions based on the SIEMENS HVdc control system under normal conditions and switches to a designed commutation failure inhibition module (CFIM) during an inverter ac fault. From the response speed point of view, since the designed CFIM does not require any proportional-integral controller, the inverter control system has a quick performance in prevention of the commutation failure. This is achieved by direct measurement of the overlap area using the waveforms of the valves anode-cathode and commuting voltages. In addition, from the accuracy aspect, the proposed method has a superior performance in comparison with the existing strategies. It is because of the fact that by direct measurement of the overlap area, variations of both direct current and the commutation inductance are considered, and hence, the unnecessary increase of the inverter reactive power consumption during the fault and the repetitive commutation failures are prevented. The practical performance and feasibility of the proposed strategy is validated through the laboratory testing, using the real-time Opal-RT hardware prototyping platform. The experimental results demonstrate that the proposed strategy can effectively inhibit the commutation failure or repetitive commutation failures under different fault types by considering the lowest possible reactive power consumption.
引用
收藏
页码:340 / 349
页数:10
相关论文
共 19 条
[1]  
[Anonymous], 2012, P INT C SUSTAINABLE
[2]   Detailed modeling of CIGRE HVDC benchmark system using PSCAD/EMTDC and PSB/SIMULINK [J].
Faruque, MO ;
Zhang, YY ;
Dinavahi, V .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (01) :378-387
[3]   Comparison of CCC and LCC in HVDC System [J].
Gao, Tao ;
Ma, Xiaochun .
2012 INTERNATIONAL CONFERENCE ON FUTURE ENERGY, ENVIRONMENT, AND MATERIALS, PT B, 2012, 16 :842-848
[4]   Modeling capacitor commutated converters in power system stability studies [J].
Gomes, S ;
Martins, N ;
Jonsson, T ;
Menzies, D ;
Ljungqvist, R .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2002, 17 (02) :371-377
[5]  
Hu Y., 2016, Encyclopedia of Reagents for Organic Synthesis, P1
[6]   Modeling and Analysis of an LCC HVDC System Using DC Voltage Control to Improve Transient Response and Short-Term Power Transfer Capability [J].
Kwon, Do-Hoon ;
Kim, Young-Jin ;
Moon, Seung-Ill .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (04) :1922-1933
[7]  
Liu C., 2016, SMART GRID HDB
[8]  
Liu Liangjun, 1998, Power System Technology, V22, P22
[9]   Capacitor Commutated Converter circuit. Configurations for dc transmission [J].
Sadek, K ;
Pereira, M ;
Brandt, DP ;
Gole, AM ;
Daneshpooy, A .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (04) :1257-1264
[10]   Fast Evaluation of Commutation Failure Risk in Multi-Infeed HVDC Systems [J].
Shao, Yao ;
Tang, Yong .