An improved control algorithm of shunt active filter for voltage regulation, harmonic elimination, power-factor correction, and balancing of nonlinear loads

被引:207
作者
Chandra, A [1 ]
Singh, B
Singh, BN
Al-Haddad, K
机构
[1] Ecole Technol Super GREPCI, Dept Elect Engn, Montreal, PQ H3C 1K3, Canada
[2] Indian Inst Technol, Dept Elect Engn, New Delhi 110016, India
[3] Tulane Univ, Dept Elect Engn & Comp Sci, New Orleans, LA 70118 USA
关键词
active filter; harmonic compensation; load balancing; power-factor correction; voltage regulation;
D O I
10.1109/63.844510
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper deals with an implementation of a new control algorithm for a three-phase shunt active filter to regulate load terminal voltage, eliminate harmonics, correct supply power-factor, and balance the nonlinear unbalanced loads. A three-phase insulated gate bipolar transistor (IGBT) based current controlled voltage source inverter (CC-VSI) with a de bus capacitor is used as an active filter (AF), The control algorithm of the AF uses two closed loop PI controllers. The de bus voltage of the AF and three-phase supply voltages are used as feed back signals in the PI controllers. The control algorithm of the AF provides three-phase reference supply currents. A carrier wave pulse width modulation (PWM) current controller is employed over the reference and sensed supply currents to generate gating pulses of IGBT's of the AF. Test results are presented and discussed to demonstrate the voltage regulation, harmonic elimination, power-factor correction and load balancing capabilities of the AF system.
引用
收藏
页码:495 / 507
页数:13
相关论文
共 29 条
[1]   Control strategy and site selection of a shunt active filter for damping of harmonic propagation in power distribution systems [J].
Akagi, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) :354-363
[2]   INSTANTANEOUS REACTIVE POWER COMPENSATORS COMPRISING SWITCHING DEVICES WITHOUT ENERGY-STORAGE COMPONENTS [J].
AKAGI, H ;
KANAZAWA, Y ;
NABAE, A .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1984, 20 (03) :625-630
[3]   An universal active power line conditioner [J].
Aredes, M ;
Heumann, K ;
Watanabe, EH .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (02) :545-551
[4]  
Arrillaga J., 1985, Power System Harmonics
[5]  
Bhattacharya S, 1995, IEEE IND APPLIC SOC, P2483, DOI 10.1109/IAS.1995.530619
[6]   Analysis and design of an active power filter for balancing unbalanced loads [J].
Bhavaraju, V.B. ;
Enjeti, Prasad N. .
IEEE Transactions on Power Electronics, 1993, 8 (04) :640-647
[7]   Control of square-wave inverters in high-power hybrid active filter systems [J].
Cheng, PT ;
Bhattacharya, S ;
Divan, DM .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1998, 34 (03) :458-472
[8]  
CLARK JW, 1990, POWER CONDITIONESRS
[9]   Control system for three-phase active power filter which simultaneously compensates power factor and unbalanced loads [J].
Dixon, JW ;
Garcia, JJ ;
Moran, L .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 1995, 42 (06) :636-641
[10]  