Cosorption Processes of Triethylene Glycol in a Packed-Bed Liquid Desiccant Dehumidifier

被引:8
|
作者
Chau, C. K. [1 ]
Worek, W. M. [2 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China
[2] Univ Illinois, Dept Mech & Ind Engn, Chicago, IL USA
来源
HVAC&R RESEARCH | 2009年 / 15卷 / 02期
关键词
REMOVAL; PREDICTIONS; SYSTEMS;
D O I
10.1080/10789669.2009.10390833
中图分类号
O414.1 [热力学];
学科分类号
摘要
The cosorption characteristics of water and toluene vapors in various concentrations of triethylene glycol (TEG) solution flowing through a packed-bed dehumidifier are investigated in this paper. A multi-component model was constructed using the reported equilibrium relationships of toluene and water vapors in TEG solutions together with the Krishna-Standart multi-component mass transfer correlation. The effects of liquid-to-air ratios, TEG inlet temperatures, air inlet temperatures were reported on the moisture and toluene removal rate as well as the moisture and toluene removal efficiency of the packed dehumidifier. Running the packed dehumidifier in a higher liquid-to-gas flow ratio generally increased the removal rates and efficiencies of both water vapor and toluene vapor from the airstream. Increasing inlet temperatures of the TEG solution led to a decrease in the removal rate of water vapor when running the packed dehumidifier at a high liquid-to-gas flow ratio. However, there was no significant change in the toluene vapor removal rate or toluene removal efficiency when the flow rate of the inlet TEG solution was increased.
引用
收藏
页码:189 / 210
页数:22
相关论文
共 50 条
  • [21] DEHUMIDIFICATION OF MOIST AIR WITH SIMULTANEOUS REMOVAL OF SELECTED INDOOR POLLUTANTS BY TRIETHYLENE GLYCOL SOLUTIONS IN A PACKED-BED ABSORBER
    CHUNG, TW
    GHOSH, TK
    HINES, AL
    NOVOSEL, D
    SEPARATION SCIENCE AND TECHNOLOGY, 1995, 30 (7-9) : 1807 - 1832
  • [22] Improved utilization of desiccant material in packed bed dehumidifier using composite particles
    Ramzy, A. K.
    Kadoli, R.
    Babu, T. P. Ashok
    RENEWABLE ENERGY, 2011, 36 (02) : 732 - 742
  • [23] An online model for predicting dynamic response of a packed liquid desiccant dehumidifier
    Zhang, Xiaobo
    Xu, Xiangguo
    Zhu, Yuxian
    ENERGY AND BUILDINGS, 2020, 224
  • [24] Dynamic operational characteristics and preliminary control of a packed liquid desiccant dehumidifier
    Zhang, Xiaobo
    Zhu, Yuxian
    Xu, Xiangguo
    Ji, Xiaosheng
    ENERGY AND BUILDINGS, 2021, 248
  • [25] Performance Evaluation of Packed Tower Liquid Desiccant Dehumidifier Based on LSSVM
    Wang, Xinli
    Lu, Jiangang
    Yang, Qinmin
    Cai, Wenjian
    Sun, Youxian
    2013 10TH IEEE INTERNATIONAL CONFERENCE ON CONTROL AND AUTOMATION (ICCA), 2013, : 987 - 990
  • [26] Design and development of wire-mesh packed bed liquid desiccant dehumidifier to reduce pressure-drop and carryover
    Sonowal, Juri
    Muthukumar, P.
    Anandalakshmi, R.
    APPLIED THERMAL ENGINEERING, 2025, 261
  • [27] Steady-state performance assessment and geometrical optimization of packed-bed liquid desiccant air dehumidification systems
    Bhowmik, Mrinal
    Gohain, Karanjeet
    Muthukumar, P.
    Saito, Kiyoshi
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2023, 38
  • [28] Analytical solution of combined heat and mass transfer performance in a cross-flow packed bed liquid desiccant air dehumidifier
    Liu, Xiao-Hua
    Jiang, Yi
    Qu, Kai-Yang
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2008, 51 (17-18) : 4563 - 4572
  • [29] THE BREAKAGE BEHAVIOR OF LIQUID MEMBRANE EMULSION IN A PACKED-BED
    LEE, EC
    HAN, KN
    HYDROMETALLURGY, 1993, 32 (02) : 233 - 245
  • [30] Quick performance prediction of liquid desiccant regeneration in a packed bed
    Gandhidasan, P
    SOLAR ENERGY, 2005, 79 (01) : 47 - 55