Measurement of Eddy-current loss coefficient PEC-R, derating of single-phase transformers, and comparison with K-factor approach

被引:43
作者
Fuchs, EF [1 ]
Yildirim, D
Grady, WM
机构
[1] Univ Colorado, Boulder, CO 80309 USA
[2] Univ Texas, Austin, TX 78712 USA
关键词
Eddy-current loss; K-factor; nonlinear load; transformer derating;
D O I
10.1109/61.847243
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A power amplifier is used to supply sinusoidal currents of different frequencies for measuring eddy-current losses of a 25 kVA single-phase transformer under short-circuit condition. Measured data show that eddy-current loss is a linear function of frequency with power of 2 and the eddy-current loss coefficient PEC-Rlinear is computed, New measurement techniques are applied to determine the derating of single-phase transformers with full-wave diode and thyristor rectifier loads, The derating of transformers has been defined such that for the (apparent, real) power transfer of a transformer the total losses are identical to the rated losses at rated temperature. A relation between apparent power, derating and K-factor is given taking into account iron-core and stray-power losses, Measured derating values are compared with computed results based on the eddy-current losses, iron-core losses, stray-power losses, and K-factors, The eddy-current loss coefficient PEC-Rnonlinear is computed from harmonics caused by diode/thyristor bridge loads.
引用
收藏
页码:148 / 154
页数:7
相关论文
共 8 条
[1]   Evaluating harmonic-induced transformer heating [J].
Bishop, MT ;
Baranowski, JF ;
Heath, D ;
Benna, SJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (01) :305-311
[2]   AGING OF ELECTRICAL APPLIANCES DUE TO HARMONICS OF THE POWER-SYSTEMS VOLTAGE [J].
FUCHS, EF ;
ROESLER, DJ ;
KOVACS, KP .
IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (03) :301-307
[3]   A new computer-aided method for the efficiency measurement of low-loss transformers and inductors under nonsinusoidal operation [J].
Fuchs, EF ;
Fei, R .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (01) :292-304
[4]   Temperature rise of small oil-filled distribution transformers supplying nonsinusoidal load currents [J].
Galli, AW ;
Cox, MD .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (01) :283-291
[5]   Computer-aided testing of electrical apparatus supplying nonlinear loads [J].
Lin, D ;
Fuchs, EF ;
Doyle, M .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1997, 12 (01) :11-21
[6]   Transformer design and application considerations for nonsinusoidal load currents [J].
Pierce, LW .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1996, 32 (03) :633-645
[7]   Modeling of magnetizing and core-loss currents in single-phase transformers with voltage harmonics for use in power flow [J].
Stensland, T ;
Fuchs, EF ;
Grady, WM ;
Doyle, MT .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (02) :768-774
[8]  
P IEEE IAS IND APPL