Indoor air quality in hospitals: a case study and a critical review of current standards

被引:10
作者
Quadros, Marina Eller [3 ]
Lisboa, Henrique de Melo [2 ]
de Oliveira, Veturia Lopes [4 ,5 ]
Schirmer, Waldir Nagel [1 ]
机构
[1] Univ Estadual Centro Oeste, Dept Engn Ambiental, BR-84500000 Irati, PR, Brazil
[2] Univ Fed Santa Catarina, Dept Engn Sanit & Ambiental, BR-88040900 Florianopolis, SC, Brazil
[3] Virginia Polytech Inst & State Univ, Blacksburg, VA 24061 USA
[4] Univ Fed Santa Catarina, Dept Microbiol & Parasitol, BR-88040900 Florianopolis, SC, Brazil
[5] Univ Nancy 1, F-54013 Nancy, France
关键词
hospital environment; bioaerosol; carbon dioxide; indoor air quality; ENVIRONMENT;
D O I
10.1590/S1413-41522009000300017
中图分类号
TV21 [水资源调查与水利规划];
学科分类号
081501 ;
摘要
The objective of this paper was to evaluate the air quality in three indoor hospital environments: a neonatal intensive care unit (ICU), an adult ICU and a surgical ward of a hospital in Florianopolis, Brazil. Carbon dioxide concentrations, exchange air flow rates as well as fungi and bacteria concentrations were measured in these rooms. Bioaerosol concentrations were evaluated throughout one-work day for each operating room. No relationship was observed between bioaerosol concentration and the period of use in the surgical ward. Average bioaerosol concentrations were of 231 UFC.m(-3) for filamentous fungi and 187 UFC.m(-3) for bacteria. All environments evaluated were, overall, in compliance with current legislations. Results allowed a critical review of the present regulations and suggestions for the establishment of a specific regulation for hospital environments in Brazil.
引用
收藏
页码:431 / 438
页数:8
相关论文
共 34 条
[1]  
Alexopoulos C. J., 1996
[2]  
[Anonymous], [No title captured]
[3]  
BARBETTA PA, 2008, ESTATISTICA CURSOC E
[4]  
Benny G.L, ZYGOMYCETES
[5]  
BRICKUS LS, 1999, QUIM NOVA, V22, P56
[6]   Indoor environmental quality in Hellenic hospital operating rooms [J].
Dascalaki, Elena G. ;
Gaglia, Athina G. ;
Balaras, Constantinos A. ;
Lagoudi, Argyro .
ENERGY AND BUILDINGS, 2009, 41 (05) :551-560
[7]  
GIODA A, 2003, THESIS U FEDERAL RIO, pF212
[8]  
Gioda Adriana, 2003, Cad. Saúde Pública, V19, P1389, DOI 10.1590/S0102-311X2003000500017
[9]  
Hellgren UM, 2006, SCAND J WORK ENV HEA, P47
[10]   Three-dimensional analysis for hospital operating room thermal comfort and contaminant removal [J].
Ho, Son H. ;
Rosario, Luis ;
Rahman, Muhammad M. .
APPLIED THERMAL ENGINEERING, 2009, 29 (10) :2080-2092