Development of Testing Method for Static Electrification Within Power Transformer Using Suspended Cellulose Fibers in Insulating Oil

被引:0
作者
Yoshida, Masanobu [1 ]
Moriguchi, Soichi [1 ]
Sato, Gaku [2 ]
Konishi, Yoshinori [2 ]
Hasegawa, Masayuki [2 ]
机构
[1] Chubu Elect Power Co Inc, Midori Ku, 20-1 Kitasekiyama Ohdaka Cho, Nagoya, Aichi, Japan
[2] YUKA Ind Co Ltd, Oota Ku, 2-3-17 Chidori, Tokyo, Japan
来源
PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 1 | 2020年 / 598卷
关键词
Power transformer; Static electrification; Cellulose fiber;
D O I
10.1007/978-3-030-31676-1_85
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes a new testing method that has been developed to estimate the quantity of electrification in a power transformer. In addition, the influence that the degradation of both a press board (PB; consists of cellulose fibers) and insulating oil has on static electrification can be evaluated by using the new testing method. In this testing method, cellulose fibers that are suspended in insulating oil in a transformer were used. These fibers might come off from the PB and the surface of insulating paper in a transformer. It was considered these cellulose fibers were useful samples for estimating the electrification level of a PB in an actual power transformer. The insulating oil was taken from a running power transformer, and cellulose fibers in the oil were filtered with a metal filter. This filtering process was isolated from the air. These cellulose fibers and insulating oil (oil with cellulose removed) were testing samples for measuring the quantity of electrification in the static electrification process. Static electrification occurs when insulating oil flows over cellulose fibers on a metal filter. The volume of electrification in the static electrification process can be known by measuring the electric current on a conductor connected between the metal filter and the ground. Experimental results showed that the volume of electrification on a degraded PB was larger than that of a new PB. Besides, there was also a tendency for the volume of electrification on degraded insulation oil (large value for electrostatic charging tendency) to be larger than that of new insulation oil.
引用
收藏
页码:908 / 916
页数:9
相关论文
共 9 条
  • [1] [Anonymous], 2009, EL TECHN RES, V1
  • [2] [Anonymous], 2000, 1215 CIGRE JWG, P170
  • [3] INVESTIGATION OF TRANSFORMER OIL ELECTRIFICATION IN A SPINNING DISK SYSTEM
    KEDZIA, J
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1989, 24 (01): : 59 - 66
  • [4] FLOW-INDUCED ELECTRIFICATION AND PARTIAL DISCHARGE MEASUREMENTS IN TRANSFORMER DUCT STRUCTURES
    LEE, MJ
    NELSON, JK
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1991, 26 (04): : 739 - 748
  • [5] FLUID ELECTRIFICATION MEASUREMENTS OF TRANSFORMER PRESSBOARD OIL INSULATION IN A COUETTE CHARGER
    MORIN, AJ
    ZAHN, M
    MELCHER, JR
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1991, 26 (05): : 870 - 901
  • [6] STREAMING ELECTRIFICATION STUDY OF TRANSFORMER INSULATION SYSTEM USING A PAPER TUBE MODEL
    OOMMEN, TV
    LINDGREN, SR
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (02) : 972 - 983
  • [7] ELECTROSTATIC CHARGING TENDENCY OF TRANSFORMER OILS
    OOMMEN, TV
    PETRIE, EM
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (07): : 1923 - 1931
  • [8] Sato G, 2010, IEEJ PES 2010
  • [9] Yoshida M, 2013, CIGRE SC A2 C4 JOINT