Characteristic analysis of heat and mass transfer process within structured packing humidifier

被引:10
作者
Chen, Junjie [1 ]
Han, Dong [1 ]
He, Weifeng [1 ]
Ji, Chao [1 ]
Si, Zetian [1 ]
Zheng, Mingrui [1 ]
Gu, Jiming [1 ]
Song, Yan [1 ]
机构
[1] Nanjing Univ Aeronaut & Astronaut, Coll Energy & Power Engn, ECRG, Nanjing 210016, Jiangsu, Peoples R China
基金
中国国家自然科学基金;
关键词
Humidifier; Heat and mass transfer; Mathematical model; Finite difference method; On-design conditions; Off-design conditions; DEHUMIDIFICATION DESALINATION SYSTEM; PERFORMANCE ANALYSIS; EVAPORATION;
D O I
10.1007/s40430-019-1864-y
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
Humidifiers are the important devices for humidifying the air both in life and industrial production. This paper focuses on the heat and mass transfer processes inside the counter-flow packing humidifier at atmospheric pressure. Based on mass and energy balance, the mathematical model for the humidifier is established. The finite difference method is first adopted to calculate the specific scales of the packing and the relevant state distribution of the gas-liquid species at on-design conditions. Thus, the heat and mass transfer performance of the humidifier is also carried out at off-design conditions. The simulation results show that the required packing height at the design parameters is 3.38 x 10(-1) m, while the supersaturation phenomenon begins at Z = 5.76 x 10(-2) m, and the humidity ratio and supersaturated humidity ratio at humidifier outlet are 1.69 x 10(-1) kg/kg and 1.64 x 10(-3) kg/kg, respectively. In addition, for off-design analysis, as the liquid-gas ratio increases, the outlet water temperature and outlet air temperature increase by 14.3% and 7.47%, respectively, and the humid air reaches saturation earlier as the saturation point falls from 5.76 x 10(-2) to 2.7 x 10(-2) m. Within the range of the simulation conditions, the maximum account of droplets entrained in the humid air reaches 1.72 x 10(-3) kg/kg, while the total packing pressure drop increases with the decrease in liquid-gas ratio. The effect of liquid-gas ratio and wet-bulb temperature of inlet air on the humidifier under design parameters can provide great reference significance for the design, optimization and regulation of humidifiers.
引用
收藏
页数:15
相关论文
共 26 条
[1]   Experimental investigation of humidification-dehumidification desalination system with corrugated packing in the humidifier [J].
Ahmed, Hossam A. ;
Ismail, I. M. ;
Saleh, Wael F. ;
Ahmed, M. .
DESALINATION, 2017, 410 :19-29
[2]  
[Anonymous], 2011, THESIS SICHUAN NORMA
[3]   Basic Analysis of Heat and Mass Transfer Characteristics of Tubular Membrane Humidifier for Proton Exchange Membrane Fuel Cell [J].
Bae, Hojune ;
Ahn, Kook Young ;
Lee, Young Duk ;
Kang, Sang Kyu ;
Yu, Sangseok .
TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2011, 35 (05) :473-480
[4]   Prediction of pressure drop in a packed bed dehumidifier operating with liquid desiccant [J].
Gandhidasan, P .
APPLIED THERMAL ENGINEERING, 2002, 22 (10) :1117-1127
[5]   Thermodynamic analysis of a novel evaporation and crystallization system based on humidification processes at ambient temperature [J].
Han, D. ;
He, W. F. ;
Ji, C. ;
Huang, L. .
DESALINATION, 2018, 439 :108-118
[6]   Thermo-economic analysis of a water-heated humidification-dehumidification desalination system with waste heat recovery [J].
He, W. F. ;
Han, D. ;
Zhu, W. P. ;
Ji, C. .
ENERGY CONVERSION AND MANAGEMENT, 2018, 160 :182-190
[7]   Parametric analysis of a humidification dehumidification desalination system using a direct-contact dehumidifier [J].
He, W. F. ;
Huang, L. ;
Xia, J. R. ;
Zhu, W. P. ;
Han, D. ;
Wu, Y. K. .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2017, 120 :31-40
[8]   Performance analysis of a water-power combined system with air-heated humidification dehumidification process [J].
He, W. F. ;
Zhang, X. K. ;
Han, D. ;
Gao, L. .
ENERGY, 2017, 130 :218-227
[9]   Experimental Research on the Heat and Mass Transfer Characteristics of Corrugated Plate Spray Humidification Air Coolers [J].
Huang, Xiaoqing ;
Zhang, Dongliang ;
Zhang, Xu .
10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 :1886-1892
[10]   Design of Cooling Towers by the Effectiveness-NTU Method [J].
Jaber, H. ;
Webb, R. L. .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1989, 111 (1-4) :837-843