Prediction of future performance of in-service XLPE cables

被引:0
作者
Gorur, RS [1 ]
Dalal, SB [1 ]
Dyer, ML [1 ]
机构
[1] Arizona State Univ, Dept Elect Engn, Tempe, AZ 85287 USA
来源
2002 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA | 2002年
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This study examines the performance of 15kV Cross-linked Polyethylene (XLPE) insulated new and aged cable (taken out from the service after 10 + years) in context with electrical tree and electrical breakdown failure of cable. The breakdown tests are performed using needle plane geometry at room temperature as well as elevated temperature of 100degreesC. The statistical technique namely regression analysis is utilized for analysis of the test results, as well as to predict the future performance and life expectancy of cables. The analytical technique, Fourier Transform Infra-Red (FTIR) spectroscopy is used to study the permanent changes in the XLPE material. This study identifies the permanent changes occurring in the material that lead to progressive degradation and/or failure in the long run.
引用
收藏
页码:421 / 424
页数:4
相关论文
共 4 条
[1]  
Bartnikas R., 1987, ASTM SPECIAL TECHNIC, V926
[2]  
BOZZO R, 1988, 1988 IEEE INT S EL I, P351
[3]   EXTENDING SERVICE LIFE OF INSTALLED 15-35 KV EXTRUDED DIELECTRIC CABLES [J].
EAGER, GS ;
KATZ, C ;
FRYSZCZYN, B ;
FISCHER, FE ;
THALMANN, E .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (08) :1997-2005
[4]   INVESTIGATION OF INSULATION DETERIORATION IN 15 KV AND 22 KV POLYETHYLENE CABLES REMOVED FROM SERVICE [J].
VAHLSTROM, W .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1972, PA91 (03) :1023-+