Research on the dynamic characteristics of electric field distribution of the ± 1100 kV Ultra high voltage converter transformer valve-side bushing using weakly ionised gas conductance model

被引:13
|
作者
Wang, Qingyu [1 ]
Liu, Peng [1 ]
Tian, Huidong [1 ]
Xie, Gengsheng [1 ]
Peng, Zongren [1 ]
Yang, Xi [2 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian, Shaanxi, Peoples R China
[2] Hefei Univ Technol, Anhui Prov Lab Renewable Energy Utilizat & Energy, Hefei, Anhui, Peoples R China
基金
中国国家自然科学基金;
关键词
HVDC SPACERS; AIR;
D O I
10.1049/hve2.12058
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Ultra high voltage (UHV) converter transformer valve-side bushings are the key equipment indirect current (DC) transmission projects, and are subjected to high voltage and large current with large number of harmonics simultaneously. The electric field distribution of converter transformer valve-side bushings is time-dependent under DC voltage, polarity reversal voltage and actual voltage waveforms, and the electric and temperature field are coupling with each other in actual operation. The dynamic characteristics of the surface charges and the electric field distribution of China's first +/- 1100 kV epoxy/paper - SF6 composite insulation converter trans former valve-side bushing under 2 h DC withstand test voltage and polarity reversal voltage were analysed considering the natural ionisation, drifting, diffusion and recombination processes of positive and negative ions in SF6 gas and air. The time-dependent electro-thermal coupling field of the bushing under the actual voltage waveform in one cycle was obtained. The rationality of the simulation method adopted was verified through type tests of the UHV converter transformer valve-side bushing. The simulation results of the paper can provide a theoretical foundation for the design of converter transformer valve-side bushings and it is of great significance to ensure the safe operation of converter stations.
引用
收藏
页码:288 / 301
页数:14
相关论文
共 5 条
  • [1] Temperature-dependent electric field distribution in ±800 kV valve-side bushing insulation for a converter transformer
    Du, Boxue
    Sun, Hanlei
    Jiang, Jinpeng
    Kong, Xiaoxiao
    Yang, Wei
    HIGH VOLTAGE, 2021, 6 (01) : 106 - 115
  • [2] Reduced Order Model of Polarity Reversal Transient Electric Field of Converter Transformer Valve-side Bushing
    Wang Q.
    Chu Z.
    Cheng J.
    Zhang H.
    Liu P.
    Peng Z.
    Gaodianya Jishu/High Voltage Engineering, 2023, 49 (06): : 2420 - 2431
  • [3] Investigation on distribution of electro-thermal coupled field and improved design of ±1100 kV converter valve-side bushing
    Liu, Xuandong
    Chen, Ming
    Liang, Chengjun
    Tang, Hao
    Zhang, Qiaogen
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2020, 14 (02) : 188 - 197
  • [4] Simulation and experimental analysis of three-dimensional temperature distribution of ±400-kV converter transformer valve-side resin impregnated paper bushing under high current
    Xie, Gengsheng
    Shi, Shifeng
    Wang, Qingyu
    Liu, Peng
    Peng, Zongren
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2022, 16 (15) : 2989 - 3003
  • [5] Analysis of multi-objective optimisation method for main insulation structure configuration scheme of valve-side winding of ultra-high voltage converter transformer considering multi-field coupling
    Yang, Lijun
    Cheng, Zhidong
    Cheng, Li
    Liao, Ruijin
    HIGH VOLTAGE, 2024, 9 (02) : 296 - 308