The Study on the Efficient HVDC Capacity Considering Extremely Low Probability of 765kV Double Circuit Transmission Lines Trip

被引:2
|
作者
Moon, Bong-Soo [1 ,2 ]
Ko, Boyung [3 ]
Choi, Jin-San [1 ]
机构
[1] Korea Elect Power Corp, Seoul, South Korea
[2] Korea Univ, Green sch, Grad Sch Energy & Environm, Seoul, South Korea
[3] Korea Univ, Sch Elect Engn, Seoul, South Korea
关键词
Double bipole HVDC transmission systems; 765kV double circuit transmission lines trip; HVDC continuous and overload capability;
D O I
10.5370/JEET.2017.12.3.1046
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The load on the power grid of South Korea is expected to grow continuously until the late 2020s, and it is necessary to increase the transfer capacity from the Eastern grid to the Seoul-Gyeonggi region by reinforcing the transmission network for the electric power system to remain stable. To this end, the grid reinforcement by two bipole LCC HVDC transmission systems have been considered on account of the public acceptability and high growth of the fault current level, even though an additional 765kV system construction is more economical. Since the probability of the existing 765kV double circuit transmission line trip is extremely low, a dynamic simulation study was carried out to estimate the efficient HVDC capacity able to stabilize the transient stability by utilizing the HVDC overload capability. This paper suggests the application plan to reduce the HVDC construction capacity with ensuring the transient stability during the 765kV line trip.
引用
收藏
页码:1046 / 1052
页数:7
相关论文
共 7 条
  • [1] Influence of AC transmission lines on parallelly erected ±500 kV HVDC double circuit transmission lines and suppression measure
    Li, Tao
    Li, Xin-Nian
    Jiang, Wei-Ping
    Gao, Jian
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (19): : 70 - 75
  • [2] Study on lightning performance for ±500 kV DC double circuit transmission lines
    Nie, Dingzhen
    Zhou, Peihong
    Dai, Min
    Wang, Dongmei
    Gaodianya Jishu/High Voltage Engineering, 2007, 33 (01): : 148 - 151
  • [3] Trip-out analysis of 110 kV double-circuit transmission lines and other lines partly on same tower
    Li, Li-Jun
    Zhu, Lin
    Wang, Jian
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (09): : 80 - 83
  • [4] Study on the Electromagnetic Environment of 1000 kV AC Double-Circuit Transmission Lines in China
    Huang, Daochun
    Ruan, Jiangjun
    Huo, Feng
    2009 IEEE/PES POWER SYSTEMS CONFERENCE AND EXPOSITION, VOLS 1-3, 2009, : 1143 - +
  • [5] Reliability Evaluation and Weak Component Identification of ±500-kV HVDC Transmission Systems With Double-Circuit Lines on the Same Tower
    Hu, Bo
    Xie, Kaigui
    Tai, Heng-Ming
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (04) : 1716 - 1726
  • [6] A study on the radio interference of the 500kV double circuit transmission lines in the Sanxia Power Station
    Liu, DC
    Li, Z
    Qian, W
    Wan, BQ
    ASIA-PACIFIC CONFERENCE ON ENVIRONMENTAL ELECTROMAGNETICS, CEEM'2003, PROCEEDINGS, 2003, : 190 - 193
  • [7] Probability parameter estimation of outage rate effects for lightning overvoltage analysis on 500 kV EHV double circuit transmission lines using neural networks
    Jaipradidtham, C.
    IPEC: 2005 INTERNATIONAL POWER ENGINEERING CONFERENCE, VOLS 1 AND 2, 2005, : 803 - 808