Improving the Energy Performance of Public Buildings Equipped with Individual Gas Boilers Due to Thermal Retrofitting

被引:4
作者
Zyczynska, Anna [1 ]
Majerek, Dariusz [2 ]
Suchorab, Zbigniew [3 ]
Zelazna, Agnieszka [3 ]
Koci, Vaclav [4 ,5 ]
Cerny, Robert [4 ]
机构
[1] Lublin Univ Technol, Fac Civil Engn & Architecture, 40 Nadbystrzycka Str, PL-20618 Lublin, Poland
[2] Lublin Univ Technol, Fac Fundamentals Technol, 38 Nadbystrzycka Str, PL-20618 Lublin, Poland
[3] Lublin Univ Technol, Fac Environm Engn, 40B Nadbystrzycka Str, PL-20618 Lublin, Poland
[4] Czech Tech Univ, Fac Civil Engn, Thakurova 7-2077, Prague 16629 6, Czech Republic
[5] Inst Technol & Business Ceske Budejovice, Okruzni 517-10, Ceske Budejovice 37001, Czech Republic
关键词
energy audits; thermal refurbishment; final energy; primary energy; energy consumption; LIFE-CYCLE ASSESSMENT; OPTIMIZATION; RENOVATION; STRATEGIES; REDUCTION; DWELLINGS;
D O I
10.3390/en14061565
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The article assesses an impact of thermal retrofitting on an improvement of the energy quality of public buildings in terms of their heating. The analysis covered a group of 14 buildings, including schools, kindergartens or offices, while energy audits were carried out for 12 of them. The indications of individual gas meters were the source of actual data for the assessment of changes in energy consumption indexes in operating conditions. The analysis showed a clear improvement in the energy quality of buildings; however, the actual effects were much lower than forecasted. The average forecasted decrease in energy consumption was supposed to be 64.3%, but the measured data showed only 37.1%. The investigation confirmed that the most complex refurbishing provided the most satisfactory decrease in energy consumption (51.4% of real decrease in energy consumption), while objects with partial thermal refurbishing reached an efficiency of only 21.8%. It was stated that in operating conditions, special attention should be paid to the manner of energy use, since different indicators of energy consumption can be obtained with the same parameters of building's balance cover. The results obtained can be further utilized in thermal-refurbishment implementation procedures. Follow-up investigations on the impact of selected parameters on energy consumption are planned.
引用
收藏
页数:19
相关论文
共 43 条
[1]  
[Anonymous], 2007, PN EN ISO 15927 4200
[2]  
[Anonymous], 2007, Building Components and Building ElementsThermal Resistance and Thermal TransmittanceCalculation Methods
[3]  
[Anonymous], 2017, 12831 EN ISO
[4]  
Asdrubali F., 2019, HDB ENERGY EFFICIENC, p441?595
[5]   Closing the gap between simulation and measured energy use in home archetypes [J].
Beagon, Paul ;
Boland, Fiona ;
Saffari, Mohammad .
ENERGY AND BUILDINGS, 2020, 224
[6]   Quantitative evaluation of deep retrofitted social housing using metered gas data [J].
Beagon, Paul ;
Boland, Fiona ;
O'Donnell, James .
ENERGY AND BUILDINGS, 2018, 170 :242-256
[7]   Energy Retrofitting Strategies and Economic Assessments: The Case Study of a Residential Complex Using Utility Bills [J].
Biserni, Cesare ;
Valdiserri, Paolo ;
D'Orazio, Dario ;
Garai, Massimo .
ENERGIES, 2018, 11 (08)
[8]  
Bloomfield V.A., 2014, Using R for numerical analysis in science and engineering
[9]  
Brom P.V.D., 2019, E3S WEB C, V111, DOI [10.1051/e3sconf/201911104025, DOI 10.1051/E3SCONF/201911104025]
[10]   On calculated and actual energy savings from thermal building renovations - Long term field evaluation of multifamily buildings [J].
Cholewa, Tomasz ;
Balaras, Constantinos A. ;
Nizetic, Sandro ;
Siuta-Olcha, Alicja .
ENERGY AND BUILDINGS, 2020, 223